Pre-Installation Items

To provide serviceability to the unit it is
recommended that the following clear-
ances be maintained:

Top and vent hood area - 36 inches.

Front and burner area - 24 inches.

Rear and primary piping areas - 12
inches.

When installing the PERFORMANCE
PLUS in a confined space, sufficient air
must be provided for proper combustion
and venting and to allow under normal
operating condition pro p e r a i r f l o w
around the product to maintain ambient
temperatures within safe limits to com-
ply with the National Fuel Gas Code
NFPA 54 - latest edition.

Flooring and Foundation

The PERFORMANCE PLUS is approved for
installation on combustible floors, but never on
carpeting.

Do not install the PERFORMANCE
PLUS on carpeting even with a metal or
wood foundation base. Fire can result
causing severe personal injury, death or
substantial property damage.

Installer should provide a solid brick or con-
crete foundation pad, at least 2 inches above
the floor level if:

-

There is a potential for the floor to
become flooded. The height of the
foundation should be such to sufficient-
ly elevate the unit.

-

The floor is dirt, sand, gravel or other
loose material.

-

The flooring is severely uneven or
sloped.

The minimum foundation size required is 24
inches x 23 inches.

Residential Garage Installations

When installing the PERFORMANCE PLUS in
a residential garage the following special pre-
cautions per N F PA 54/ANSI Z223.1 must be
t a k e n :

-

Mount the unit with a minimum 18
inches above the floor level of the
garage. Ensure the burner and ignition
devices / controls are no less than 18
inches above the floor level.

-

Locate or protect the unit in a matter
so it cannot be damaged by a moving
v e h i c l e .

WARNING

WARNING

BEST PRACTICES

6

This manual is related to the following products: