7 spillage check, 8 final review – Glow-worm Miami 4 User Manual
Page 14
14
221904D
9499
Diagram 7.1
7.1 Spillage Check
Note:
1. Take care. The appliance gets hot during testing.
2. To carry out the test you will need a 500mm emplume
tube and a torch.
TEST: WHERE NO FAN IS PRESENT
Close all outside doors and doors and windows in the room in
which the appliance is installed.
Light the fire front only. After 5 minutes apply spillage test.
Position the smoke match tip under the fire front flue duct on the
draught diverter lip by inserting the emplume tube 380mm
through the side louvres, see diagram 7.1. During test smoke
should be drawn into the draught diverter and between the fire
front flue duct and the draught diverter lip. If spillage occurs
leave fire front alight for up to a further 10 minutes and repeat
tests.
Next, light the boiler only and after 10 minutes apply spillage test
by positioning smoke match tip as described above, and shown
in diagram 7.1. If spillage occurs, leave the boiler alight for up
to a further 5 minutes and repeat test.
Now light the boiler and fire front. After 10 minutes apply
spillage tests by positioning smoke match tip as described
above, and shown in diagram 7.1. During tests smoke should
be drawn into the boiler draught diverter. If spillage occurs,
leave the boiler and fire front alight for up to a further 5 minutes
and repeat tests.
Note: If spillage does occur smoke will be visible exiting the top
of the fire casing.
TEST. WHERE A FAN IS PRESENT
(A fan means an extractor fan, or a fan for other open flued
appliances, or a circulating fan for a warm air unit, whether or not
gas fired). With the fan switched off carry out the appropriate
spillage test with all doors and windows closed, as above.
If the above tests are satisfactory continue as follows,
Open all doors connecting the room containing the appliance
and the room in which the fan is fitted. Close all other doors and
windows in the premises.
If the fan is in the same room as the appliance close all doors
and windows in that room. Switch on fan and repeat spillage
test as above.
In ALL cases, if spillage continues after the specified test
periods steps MUST be taken to put right the fault(s).
Possible causes include, flue obstructions, down draught or
restricted fresh air supply into the room.
7 Spillage Check
Please ensure the “Benchmark” logbook (supplied with Back
Boiler Unit) is completed and left with the user.
Make sure that the dress guard is securely in position.
Check the operation of the fire at all control positions.
Visually inspect the appliance. Clean off any marks incurred
during installation.
Advise the customer how to operate the fire and boiler.
Explain to the customer that the appliance has a flame failure
and spillage monitoring system. Point out the explanation of this
system in the "Instructions for Use". Advise that if the appliance
goes out for any reason, they must wait at least three minutes
before relighting. Stress that if the monitoring system repeatedly
shuts off the appliance that it must be switched off and their local
installation or service organisation must be contacted or the
local gas undertaking contacted.
Advise that the fire may give off a slight odour while new. This
is quite normal and it will disappear after a short period of use.
EMPLUME
TUBE
DRAUGHT
DIVERTER LIP
SMOKE
MATCH
TIP
380mm
VIEW ON ARROW 'A'
(FIRE REMOVED FOR CLARITY)
FIRE FRONT
FLUE DUCT
A
MIAMI ILLUSTRATED
Advise the customer that they should read the Instructions for
Use before operating the fire and always follow the advice in the
section headed "Cleaning your fire".
Advise the user that the appliance can be lit with a match if
necessary by inserting it through the central opening at the
bottom of the radiant box.
Recommend that the appliance should be serviced and the
chimney inspected by a competent person (In the UK a CORGI
registered person) at least annually.
If the appliance is in premises in the United Kingdom occupied
by a tenant, point out that by law a landlord must have any gas
appliance, flue and pipework which is situated in a tenant’s
premises checked for safety at least every 12 months.
Mention that the radiants may become brown with use, that this
is quite normal and has no adverse effect and that they can be
replaced without removing the case, refer "Instructions for
Use", replacing radiants section.
Reminder- leave these instructions and the “Benchmark” logbook
with the user.
8 Final Review