beautypg.com

Assembly overview – Echelon SmartServer 2.2 Hardware User Manual

Page 14

background image

Assembly Overview

You need to mount the SmartServer and connect it to an IP network before you can configure it and
begin using its embedded applications. This section lists the general steps required to mount and
connect the SmartServer. These steps are then detailed in the referenced sections.

1. Mount the SmartServer inside a suitable enclosure. For more information on this step, see the

next section, Mounting the SmartServer.

2. Connect the screw terminals on the SmartServer.

a. You must connect the power screw terminals for all SmartServer models as described in the

Power Supply section in this chapter.

b. If you are assembling an FT-10 model of the SmartServer, you must connect a L

ON

W

ORKS

FT-10 channel to the LON A

®

/PLT + and LON B

®

/PLT - screw terminals on the hardware

(screw terminals 18 and 17). For more information, see L

ON

W

ORKS

Network in this chapter.

If you are assembling the PL-20 model of the SmartServer with the external coupling option,
you can connect twisted pair wiring between screw terminals 17 and 18 and a single-phase or
three-phase external coupler. For more information, see L

ON

W

ORKS

Network in this chapter.

The internal coupling PL-20 model of the SmartServer communicates through the power
supply and therefore does not require any additional connections.

c. Optionally, you can connect the screw terminals for the RS-232/RS-485 serial ports, digital

outputs, pulse meter inputs, digital inputs, and +12V <20mA output on the hardware as
described in the respective sections in this chapter for each of these connections.

3. If you are not using an internal analog modem for the SmartServer, connect the Ethernet port on

the SmartServer. Connect one end of an Ethernet cable to the Ethernet port on the SmartServer,
and then connect the other end to an Ethernet switch or hub that can communicate with your
computer (IP network). The Ethernet port on the SmartServer is auto-switching; therefore, you
can use a straight-through or crossover Ethernet cable. For more information on this step, see
Connecting the Ethernet Port in this chapter.

4. Optionally, you can connect the console port on the SmartServer. Connect one end of a RS-232

null modem cable to the console port on the SmartServer, and then connect the other end to one of
the COM ports on your computer. You can then use a terminal emulation program such as
PuTTY on your computer to access the SmartServer’s console application and configure the
SmartServer. The default communication properties for the SmartServer are 9600- 8-None-1-
None. For more information on this step, see Connecting the Console Port in this chapter.

5. If you are using a SmartServer that has a built-in analog modem, connect the telephone port on the

SmartServer. For more information on this step, see Connecting the Telephone Line Port in this
chapter.

6. Apply power to the SmartServer. For more information on this step, see Applying Power to the

SmartServer in this chapter.

7.

Connect your SmartServer to an IP network.

a. If your computer is not on the subnet as your SmartServer, open a command prompt with

administrator privileges and type the following command:

route add 192.168.1.0 mask 255.255.255.0 %computername%

To open a command prompt with administrator privileges, click Start, type cmd in the search
box, right-click the cmd.exe, and then select Run as Administrator. If you receive a “The
parameter is incorrect” error after entering the route command, replace %computername%
with the IP address of your computer.

2