1.4 Sequence of Operation

Operational State

User Interface Display

Explanation

Boiler operates in standby mode until

demand for Central Heat (CH) or

Domestic Hot Water (DHW) is detected.

CH or DHW pump is turned on based on

type of heating demand.
(CH call is illustrated)

Control Module compares supply

temperature to set point. Boiler proceeds

to ignition if supply temperature is less

than set point.

Combustion Air Blower speed

modulates to pre-purge setting for 15

seconds.

Sparking initiated sequence.

S t a n d b y : N o D e m a n d

Heat

Demand?

DHW CH

Pump on

Supply

Temperature

15 Second

Prepurge

Ignition

Sparking

No

Yes

No

Yes

After 2 seconds

APPENDIX A - CONTROL MODULE