Figure 11-3 Condensate Trap - 050,075,100,150,200

Flue Pipe

Temperature

Sensor

Hose Barb w/Cap

Coupling

Condensate Collector

Condensate

Trap Connection

To Condensate

Collector

Flexible Gas Line

11.2 Annual Shut Down Procedure

• Follow instructions “To Turn Off Gas To Appliance”

unless

boiler is also used to supply domestic hot water. See

section 10.

• Drain system completely if system does not have

antifreeze when heating system is to remain out of

service during freezing weather.

• Drain condensate lines when boiler is to be exposed to

freezing temperatures.

WARNING

Following service procedures must be performed

by qualified service agent. Boiler owner shall not

attempt these steps. Failure to do so could result in

death or serious injury.

!

11.3 Annual Inspection and Cleaning of Boiler

Components

• Obtain Burner Inspection Kit. Follow kit instructions to

prepare for examination and cleaning.

• Burner and heat exchanger inspection and cleaning.

• Remove gasket and burner. Allow burner to clear top

lip of chassis.

• Remove any residual sleeve and/or gasket material

from removed burner.

• Clean burner using air hose directed into top of

burner opening to dislodge any debris in burner ports.

Inspect burner for foreign matter in flame ports or

inside burner. Remove foreign matter by blowing with

compressed air or vacuuming. Replace burner if it

cannot be cleaned or is showing deterioration.

• Clean heat exchanger with low pressure water spray.

Use flexible handle nylon brush to loosen sediment

and oxide on all accessible heating surfaces of heat

exchanger. Take care not to get brush stuck in heat

exchanger.

• Remove any remaining loosened sediment using shop

vacuum with snorkel attachment.

• Clean condensate collector if significant debris found in

heat exchanger.

• Expand upper spring tension clip of condensate trap

using hose clamp pliers. Disconnect condensate trap

from condensate collector. See figures 11-3 & 11-4.

• Disconnect wire harness from vent temperature

sensor. See figure 11-3 .

• Loosen upper hose clamp securing condensate

collector to flue pipe using 3/8" socket with 6"

extension.

Figure 11-4 Condensate Trap - 299

11 - GENERAL MAINTENANCE AND CLEANING

Condensate Trap Connection

To Condensate Collector

Flexible Gas Line

Condensate Collector