• Install discharge piping from safety relief valve. See

figure 5-2.

• Use ¾" or larger pipe.
• Use pipe suitable for temperatures of 375°F (191°C)

or greater.

• Individual boiler discharge piping shall be independent

of other discharge piping.

• Size and arrange discharge piping to avoid reducing

safety relief valve relieving capacity below minimum

relief valve capacity stated on rating plate.

• Run pipe as short and straight as possible to location

protecting user from scalding and properly drain

piping.

• Install union, if used, close to safety relief valve outlet.
• Install elbow(s), if used, close to safety relief valve

outlet and downstream of union (if used).

• Terminate pipe with plain end (not threaded).

5.4 Trim Piping

• Temperature - Pressure Gauge. Install temperature

pressure gauge using nipple, tee and bushing provided

with boiler. See figure 5-3.

• Drain Valve. Install drain valve using nipple, tee and

bushing provided with boiler. See figure 5-3.

5.5 System Piping

• See Table 3 for basic system piping configurations.
• Systems with automatic fill valves require back flow

prevention device.

• Single boiler system. See figures 5-4, 5-5, 5-6, 5-7A, & B

for general guidance. Additional considerations:

• Boiler control is designed for single central heating

pump. Installer responsible for integration of

multiple central heating pumps.

• Boiler control allows domestic hot water

prioritization. Function could be lost if central

heating pump not directly connected to control

system.

• Multiple boiler system. See figure 5-8A, B & C for general

guidance. Additional considerations:

• Control system requires equivalent water

temperatures entering each boiler to properly

sequence and adjust system supply temperature.

• Install multi boiler sensor kit. See "Parts, Kits &

Optional Accessories" manual for part number.

• Heating system with existing primary loop, close internal

primary loop ball valve.

• Heating system without existing primary loop, leave internal

primary loop ball valve open to use internal primary loop.

FIGURE 5-3 Temperature Pressure Gauge and Drain

Valve Installations

Temperature Pressure

Gauge shown at

System Supply

Connection

Check Local Codes

For Maximum

Distance To Floor

WARNING

Burn and scald hazard. Safety relief valve could

discharge steam or hot water during operation.

Install discharge piping per these instructions.

!

FIGURE 5-2 Safety Relief Valve Discharge Piping