beautypg.com

Dunkirk Helix VLT Vertical Laser Tube, Wall Hung Modulating Condensing Boiler User Manual

Page 49

background image

49

Screen Display

Explanation

Go to Page For

Troubleshooting

Low water cutoff sees no water.

Go to Page 56

Flue temperature sensor sees temperature

higher than 200°F.

Go to Page 57

Return water temperature sensor sees

temperature higher than 200°F.

Go to Page 58

Control board internal error. Power down then

power up boiler. If error repeatedly occurs

replace control module.

Replace Control

Module

Boiler is powered by three wires, hot, neutral

and ground. E44 displays when neutral wire is

not neutral.

Go to Page 58

Control board sees power supply frequency not

in range of 59 to 61 Hz.

Go to Page 59

Boiler power supply ground wire is not

grounded.

Go to Page 60

Control board internal error. Power down then

power up boiler. If error repeatedly occurs

replace control module.

Replace Control

Module

Supply temperature sensor is open. No

continuity.

Go to Page 60

Return water temperature sensor is open. No

continuity.

Go to Page 61

Flue temperature sensor is open. No

continuity.

Go to Page 62

Supply water temperature sensor is shorted.

'0' Ohm

Go to Page 62

Return water temperature sensor is shorted.

'0' Ohm

Go to Page 63

Flue temperature sensor is shorted. '0' Ohm

Go to Page 63

Reset button was pressed too many times.

Error Clears in 1-2

minutes

Fault detected in blower motor system.

Go to page 59

Blocking Error

F l u e G a s E r r o r

E 39

13 - TROUBLE SHOOTING