6.8 Multiple Boiler Venting Installation

• Multiple boiler application boiler can vent individually

or use common vent pipes.

• If boilers vent individually follow guidelines as

described in figures 6-1 through 6-7.

• If boilers vent through common vent pipes, as shown

in Figure 6-17, choose common vent pipe per Table 8.

Choose size from Table 9 for pipes between boiler and

common vent pipes.

• Longest individual vent lengths and common vent

length together must be shorter than 100 ft. (30m).
H + L ≤ 100 ft (30m) (See figure 6-17)

• Each boiler must have flow check valve to prevent flue

gas back flow.

• External terminals follow same rule as single boiler

venting as described in Section 6.6 and 6.7

FIGURE 6-17 Mulitple Boilers With Common Venting Pipe

Model

Minimum

Diameter

050

2" (51mm)

075

3" (73mm)

100

3" (73mm)

150

3" (73mm)

200

3" (73mm)

299

3" (73mm)

Table 8 - Minimum Diameter for Individual

Boiler in Common Venting System

Total

Firing

Rate

Minimum

Diameter of

Common vent

pipes if

L< 50 ft (16m)

Minimum

Diameter of

Common vent

pipes if

L>50 ft (16m)

400

4" (101mm)

5" (127mm)

600

5" (127mm)

6" (152mm)

800

1000

6" (152mm)

7" (177mm)

1200
1400
1600

7" (177mm)

8" (203mm)

1800
2000

Table 9 - Common Venting Pipe Diameters

L

H

6 - COMBUSTION AIR AND VENT PIPING

Flow Check

Valve

Flow Check

Valve

Flow Check

Valve

12" (305mm)

Anticipated

Snow Line

Vent

Combustion

Air

Ground Level