3.13 Offset Calibration

@Description

To correct the offset errors of AD converter by using the offset
calibration.

@Syntax

$(Addr)1

$

Command leading code

(Addr)

Address ID

1

Offset calibration.

@Response

!(Addr)
or
?(Addr)>

!

Command is valid.

?

Command is invalid.

(Addr)

Address ID.

@Example

User command:

$061

Response:

!06


To perform the offset calibration for analog input module at specified
address 06 (Hex).

Note:

To perform the calibration, a proper input signal should be
connected to the analog input module. Different input range
have different input voltage, detail refer chapter 5
Calibration” .

(6011/D, 6012/D, 6013 C4.6