9 read synchronized data – ADLINK ND-6017 User Manual
Page 54
46
• Command Set
3.9 Read Synchronized Data
@Description
After a synchronized sampling command #** was issued, you can read
the sampled value that was stored in the register of the module at
specified address.
@Syntax
$(Addr)4
$
Command leading code.
(Addr)
Address ID
4
Read synchronized data.
@Response
>(Addr)(Status)(Data)
or
?(Addr)
>
Command is invalid.
?
Command is invalid or no synchronized sampling
command was issued.
(Addr)
Address ID.
(Status)
0: Data has been sent at least once before.
1: Data has been sent for the first time since a
synchronized sampling command was
issued. (1-character)
(Data)
There are four types of Data format, refers to
Chapter 4 for details.
@Examples
User command:
$064
Response:
>060+1.6888
Read synchronized data at address 06H, analog input module send its
analog input data +1.6888 (units). Status is 0 means it has sent the
same data at least once. The current units is set by the data format.
User command:
$064
Response:
>061+1.6888
Read synchronized data at address 06H, analog input module send its
analog input data +1.6888 (units). Status is 1 means it is the first time
that the data has been sent. The current units is set by the data format
(6011/D, 6012/D, 6014D)