Command Set

41

3.4 Read Configuration

@Description

Read the configuration of module on a specified address ID.

@Syntax

$(Addr)2>

$

Command leading code

(Addr)

Address ID.

2

Command code for reading configuration

@Response

!(Addr)(InputRange)(BaudRate)(DataFormat)
or
?(Addr)>

!

Command is invalid.

?

Command is invalid.

(Addr)

Address ID.

(InputRange)

Current setting of analog voltage input, refers
to Table 3-1 for details.

(BaudRate)

Current setting of communication baud rate,
refers to Table 3-2 for details.

(DataFormat)

Current settings of checksum, integration time
and output data format, refers to Figure 3-1 for
details.

@Example

User command:

$302

Response:

!30050600

!

Command is valid.

30

Address ID.

05

Analog input range is

±2.5 V.

06

Baud rate is 9600 bps.

00

checksum is disable.

(6011/D, 6012/D, 6013

6014D, 6017, 6018)