LP Gas Only

AWARNING

U/

Explosion Hazard

Have a qualified person make sure L.P. gas pressure

does not exceed 13” water column.

Examples of a qualified person inciude: licensed

plumbers, authorized gas company personnei, and

authorized service personnei.

Faiiure to do so can resuit in death, expiosion, or fire.

Liquefied petroleum gas is over 50% heavier than air
and in the occurrence of a leak in the system, the gas

will settle at floor level. Basements, crawl spaces, closets

and areas below ground level will serve as pockets for
the accumulation of gas. Before lighting an L.P. gas water
heater, smell all around the appliance at floor level. If you
smell gas, follow the instructions as given in the warning
on the front page.

When your L.P. tank runs out of fuel, turn off the gas at
all gas appliances including pilot lights. After the tank is

refiiled, all appliances must be re-lit according to their
manufacturer’s instructions.

Table 1

Natural Gas Pipe Capacity Table (Cu. Ft./Hr.)

Capacity of gas pipe of different diameters and lengths in cu.
of 0.60 (natural gas).

ft. per hr. with pressure drop of 0.3 in. and specific gravity

Nominal Iron Pipe

Length of Pipe, Feet

Size, in.

10

20

30

40

50

60

70

80

90

100

125

150

175

200

1/2

132

92

73

63

56

50

46

43

40

38

34

31

28

26

3/4

278

190

152

130

115

105

96

90

84

79

72

64

59

55

1

520

350

285

245

215

195

180

170

160

150

130

120

110

100

1-1/4

1050

730

590

500

440

400

370

350

320

305

275

250

225

210

1-1/2

1600

1100

890

760

670

610

560

530

490

460

410

380

350

320

After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour

required for the gas input rating of the water heater. By formula:

r» c* D Lj D

- A

Gas Input of Water Heater (BTU/HR)

Cu. Ft. Per Hr. Required= —□—

t

-—m

----------- rF—

Heating Value of Gas (BTU/FP)

The gas input of the water heater is marked on the water heater data plate. The heating value of the gas (BTU/FT)
may be determined by consulting the local natural gas utility.

Table 2

LP Gas Capacity Table

Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water

column pressure). Based on a pressure drop of 0.5 inch water column.

Nominal

Iron Pipe

Size, in. in

Length of Pipe, Feet

M.

M.

1/2

275

189

152

129

114

103

96

89

83

78

69

63

3/4

576

393

315

267

237

217

196

185

173

162

146

132

1

1071

732

590

504

448

409

378

346

322

307

275

252

1-1/4

2205

1496

1212

1039

913

834

771

724

677

630

567

511

Example: Input BTU requirement of the water heater 100,000 BTUH.

Total pipe length, 80 feet = 3/4" IPS required.

Additional tables are available in the latest edition of the "National Fuel Gas Code", ANSI Z223.1.

10