Carrier Streamline Scroll 69NT20-531-300 User Manual
Page 51

3-26
T-309
Table 3-9 DataCORDER Pre-Trip Result Records
Test
No.
TITLE
DATA
1-0
Heater On
Pass/Fail/Skip Result, Change in current for Phase A, B and C
1-1
Heater Off
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
2-0
Condenser Fan On
Pass/Fail/Skip Result, Water pressure switch (WPS) -- Open/Closed,
Change in currents for Phase A, B and C
2-1
Condenser Fan Off
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
3-0
Low Speed Evaporator Fan
On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
3-1
Low Speed Evaporator Fan
On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
4-0
High Speed Evaporator Fan
On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
4-1
High Speed Evaporator Fan
On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
5-0
Supply/Return Probe Test
Pass/Fail/Skip Result, STS, RTS, SRS and RRS
5-1
Secondary Supply Probe Test
Pass/Fail/Skip
5-2
Secondary Return Probe Test
Pass/Fail/Skip
6-0
Discharge Thermistor Test
Pass/Fail/Skip
6-1
Suction Thermistor Test
Pass/Fail/Skip
6-2
Discharge Pressure Sensor
Test
Pass/Fail/Skip
6-3
Suction Pressure Sensor Test
Pass/Fail/Skip
6-4
Compressor Current Draw
Test
Pass/Fail/Skip
6-5
Suction Modulation valve Test Pass/Fail/Skip
6-6
Economizer Valve Test
Pass/Fail/Skip
6-7
Unloader Valve Test
Pass/Fail/Skip
7-0
High Pressure Switch Closed
Pass/Fail/Skip Result, AMBS, DPT or CPT (if equipped)
Input values that component opens
7-1
High Pressure Switch Open
Pass/Fail/Skip Result, STS, DPT or CPT (if equipped)
Input values that component closes
8-0
Perishable Mode Heat Test
Pass/Fail/Skip Result, STS, time it takes to heat to 16_C (60_F)
8-1
Perishable Mode Pull Down
Test
Pass/Fail/Skip Result, STS, time it takes to pull down to 0_C (32_F)
8-2
Perishable Mode Maintain
Test
Pass/Fail/Skip Result, Averaged DataCORDER supply temperature
(SRS) over last recording interval.
9-0
Defrost Test
Pass/Fail/Skip Result, DTS reading at end of test, line voltage, line
frequency, time in defrost.
10-0
Frozen Mode Heat Test
Pass/Fail/Skip Result, STS, time unit is in heat.
10-1
Frozen Mode Pull Down Test
Pass/Fail/Skip Result, STS, time to pull down unit to --17.8_C (0_F).
10-2
Frozen Mode Maintain Test
Pass/Fail/Skip Result, Averaged DataCORDER return temperature
(RRS) over last recording interval.