E. EXHAUST REQUIREMENTS
Exhaust duct work should be designed and installed by a qualified technician. Improperly sized duct work
will create excessive back pressure which results in slow drying, increased use of energy, overheating of the
dryer, and shutdown of the burner by the airflow (sail) switch, burner hi-limit, or lint chamber hi-heat
protector thermostat. Refer to the following illustrations for details.
CAUTION: IMPROPERLY SIZED OR INSTALLED EXHAUST DUCT WORK CAN
CREATE A POTENTIAL FIRE HAZARD.
MULTIPLE DRYER VENTING
WITH AN "A" DIAMETER EXHAUST CONNECTIONS AT COMMON DUCT
N0, OF DRYERS
8
7
6
5
4
3
2
1
MINIMUM CROSS
SECTION AREA (SO,IN,)
B
D
F
H
j
L
N
P
MINIMUM ROUND
DUCT DIAMETER (IN,)
C
E
G
1
K
M
0
0
VERTICAL
HORIZONTAL
WALL
2 X DIA CLEARANCE
2 X D CLEARANCE
ROOF
TUMBLER EXHAUST MUST ENTER MAIN
EXHAUST DUCT AT A Z5° ANGLE,
1^ SEE NOTE B
FOR MINIMUM DISTANCES
BETWEEN DUCTS
IMPORTANT: NO MORE THAN 8 DRYERS CAN
BE CONNECTED TO ONE COMMON DUCT (VENT),
MAN3725
FORMULAS TO CALCULATE DUCTING CROSS SECTIONAL AREA
CROSS SECTIONAL AREA OF A ROUND DUCT = ,785 x DIA^
CROSS SECTIONAL AREA OF A RECTANGULAR DUCT - WIDTH x HEIGHT
HEIGHT
—IWIDTHh“
NOTE A: OPENING MUST BE TWO (2) INCHES LARGER THAN DUCT (ALL THE WAY AROUND), THE DUCT
MUST BE CENTERED WITHIN THIS OPENING,
NOTE B, 75 lbs-38 VA
NOTE B, 50 lbs,-38 1/4", 30 lbs-31 3/8"
75 lbs.
Dryer Exhaust Duct Size: 8"
Dryer Air Flow: 1,200 cfm
A
B
c
D
E
F
G
H
1
J
K
L
M
N
O
P
Q
8"
530
26
455
24
455
24
380
22
315
20
255
18
200
16
115
12
50 lbs.
30 lbs.
Dryer Exhaust Duct Size: 8"
Dryer Air Flow: 600 cfm
A
B
c
D
E
F
G
H
1
J
K
L
M
N
0
P
Q
8”
380
22
315
20
315
20
255
18
200
16
155
14
115
12
80
10