beautypg.com

A warning – Carrier 58PAV User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

SUPPLY

AIR

For Example:

VENT THROUGH ROOF

(CATEGORY I) OR WALL
(CATEGORY III)

I I I
I I I
I I I

~r

12 MAX

i

1

so

IN.

Ш

PER 1000

BTUH*

INTERIOR
HEATED
SPACE

6 IN. MIN

(FRONT) t

1 SO IN.
PER 1000
BTUH*

TI

i

1

RETURN AIR^---

12 MAX

* Minimum opening size is 100 square in. with

minimum dimensions of 3 in.

1 Minimum of 3 in. when type-B vent is used.

A89012

Fig. 2—Air For Combustion and Ventilation

(Inside Air)

c. If the furnace is installed on a raised platform to provide a

return-air plenum, and return air is taken directly from the
hallway or space adjacent to the furnace, all air for
combustion must come from outdoors.

2. All air from outside the structure:

a. If combustion air is taken from outdoors through vertical

ducts, the openings and ducts MUST have at least 1 sq in.
of free area per 4000 Btuh of the total input for all
equipment within the confined space. (See Fig. 3.)

For Example:

58PAV FURNACE

INPUT BTUH

FREE AREA PER OPENING

(SQ IN.)

ROUND PIPE

(IN. DIA)

44,000

11.0

4

66,000

16.5

5

88,000

22.0

6

110,000

27.5

6

132,000

33.0

7

154,000

38.5

7

b. If combustion air is taken from the outdoors through

horizontal ducts, the openings and ducts MUST have at
least 1 sq in. of free area per 2000 Btuh of the total input
for all equipment within the confined space.

58PAV FURNACE

INPUT BTUH

FREE AREA PER OPENING

(SQ IN.)

ROUND PIPE

(IN. DIA)

44,000

22.0

6

66,000

33.0

7

88,000

44.0

8

110,000

55.0

9

132,000

66.0

10

154,000

77.0

10

When ducts are used, they must be of the same cross-sectional area

as the free area of the openings to which they connect. The
minimum dimension of rectangular ducts must not be less than 3
in. (See Fig. 3.)

A WARNING

Do not install the furnace on its back as safety control
operation are adversely affected. Never connect return-air
ducts to the back of the furnace. Failure to follow this warning
can cause a fire, personal injury, or death.

Step 3—Filter Arrangement

The factory-supplied filter(s) is shipped in the blower compart­
ment. Determine location for the filter and move filter retaining
hardware, if necessary, before attaching the return-air duct. After
the return-air duct has been connected to the furnace, install the
filter(s) inside the furnace blower compartment. See Fig. 4 for side
return application and Fig. 5 for bottom return application.

COMBINATIONS OF OPENINGS:

A&B C&D D&E

A89013

Fig. 3—Air For Combustion and Ventilation

(Outside Air)