Step 6 — make piping connections, 6 — liquid and suction line locations in top panel – Carrier 38JB User Manual
Page 4
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 2 — Electrical Data (60-Hz, 3-Ph)
FLA
-
Kw
—
LRA —
MCA -
UNIT
VOLTS*
COMPRESSOR
FAN
UNIT POWER
SUPPLYt
38 JB
Model
Nameplate
Min
Max
RLA
LRA
FLA
Kw
MCA
Max Fuse
Amps
520
208-230
187
254
64 0
266
16 2
3 73
~ 97 5‘
150
016
610
460
414
508
28 6
120
7 1
3 73
43 4
70
110
575
518
632
23 6
96
5 6
3 73
35 6
50
520
208-230
187
254
44 3
r 170
, g --
3 73
117 0
150
024
610
460
414
508
20 0
77
7 1
3 73
52 6
70
110
575
518
632
15 7
62
5 6
3 73
41 5
50
RLA
Full Load Amps (fan motor)
Total Kilowatts
Locked Rotor Amps
Minimum Circuit Amps Complies with NEC, Section
430-24
Rated Load Amps (compressor)
‘Units are suitable for use on electrical systems where voltage
supplied to the unit terminal block is not below minimum or
above maximum
fFuse only
NOTES
1 Control circuit breaker size is 3 2 amps for all units
2 Unit 38JB024 has 2 compressors; RLA and LRA values apply
for each
UNPOADER
suction
.
line
, , .C.Q.IyiPRESSOR
38JB016
SUCTION LINES
COMPRESSOR
38JB024
Fig. 5 — Piping Connections
Step 6 — Make Piping Connections
Connect condensing unit to a fan coil unit using
field-supplied refrigerant grade tubing. Do not use
damaged or contaminated tubing. Evacuate or
purge field-supplied tubing.
The 38 JB is shipped with a holding charge in the
condensing coil and compressor. When using head
pressure dampers, connect line to head pressure-
Fig. 6 — Liquid and Suction Line Locations
in Top Panel
actuated piston operator prior to pumping system
down. Evacuate remainder of system before
charging.
CONNECT REFRIGERANT LINES — See Fig. 5.
When suction lines are piped thru the front or top
of the 38JB016, one 1-3/8 in. 90° elbow is required;
two 1-1/8 in. 90° elbows are required on the
38JB024. See Fig. 6 for hole locations.
When liquid lines are piped thru the front of unit
elbows are not required. When liquid lines are piped
thru top of unit, two 5/8-in. 90° elbows are
required. See Fig. 1 and Fig. 6 for line locations.