Transfer Switch & Engine Generator

Automatic (remote) Operation

This procedure checks the electrical operation of

the automatic transfer switch. If the actual operation

does not follow this procedure, consult the trouble-

shooting section in the transfer switch manual.

. Turn on the preferred source (utility) circuit

breaker. The

Utility Acceptable Light should now

come on as well as the

Load On Utility Light. If

these lights fail to come on recheck your incoming

power to insure you have 240 volts nominal. If not,

troubleshoot your utility source before continuing.

2. Press and release the

Auto button on the

engine control module (ECM). The auto mode icon

will appear on the screen. The unit is now ready to

be operated from the Automatic Transfer Switch.

3. Turn on the alternate source (generator) circuit

breaker.

******************

***** WARNING *****

******************

PERSONAL INJURY HAZARD - Install front cover

in transfer switch before operation. An electrical sys-

tem fault could cause a flash and severe personal

injury.

DESCRIPTION

The digital controller provides sensing, timing, and

control functions for the ATS. This micro-processor-

based controller includes built-in control buttons and

status lights for control of the ATS and the generator.

PUSH BUTTONS

On the front control display are three push buttons

that control the operation of the generator and the

ATS.

**** CAUTION ****

Before using the transfer test button, be sure

that conditions are safe for running the genera-

tor and for load transfer

TRANSFER TEST Use this button to test the

system. This operation starts the generator and

transfers the load. The controller is shipped with a

load transfer set by default. Changing the exercise

without a load will be discussed later. Be sure that

conditions are safe to do this operation.

BYPASS TIME DELAY Use this button to cancel

the active time delay or exercise period (stops the

generator after cooldown).

SET ENGINE EXERCISER Use this button to set

the automatic exerciser.

INDICATOR LIGHTS

On the front control display are five lights that indi-

cate the status of the sources and the ATS.

UTILITY ACCEPTABLE This light indicates that

the utility voltage is acceptable for connection to the

load.

GENERATOR ACCEPTABLE This light indicates

that the generator voltage and frequency is accept-

able for connection to the load.

LOAD ON UTILITY This light indicates that the

generator voltage is acceptable for connection to the

load.

LOAD ON GENERATOR This light indicates that

the generator voltage and frequency is acceptable

for connection to the load.

ASCO 185 DIGITAL CONTROLLER