Start up procedure – Winco ULPSS15B2W/E User Manual
Page 15
5
088-00
60706-207
START UP PROCEDURE
Engine Generator Set only
The engine control module (ECM) is manufactured
by Deep Sea Electronics. Model 30 is used on
this engine generator set. See picture below. Ad-
ditional information on the DSE 30 is on pages 4,
9-2.
Manual Operation
Press and release the red
Stop/Reset button. Then
press and release the green
Start Engine button.
The engine generator will crank and start automati-
cally. If the engine fails to start see Fault Codes on
page 20 to correct the problem before proceeding.
With the engine running smoothly, check the no load
voltage and frequency at wire # and # 4 (L2 and
L6 in the ASCO ATS) on the generator terminal block
in the ATS. The voltage should be 240 volts plus or
minus nominal. The frequency should be between
6.5 to 62 hertz (Hz). The voltage should also be
checked between the hot terminals (L2 and L6) and
the neutral to be certain of a balanced voltage output
and a solid neutral connection. The voltage should
be about on half of the line to line voltage. See pic-
ture below for frequency adjustments.
** NOTICE **
If for any reason during the check out procedures
the voltage and frequency are not correct, press the
red
Stop/Reset button and correct the trouble before
proceeding.
After verifying the voltage and frequency are correct,
press the
Stop/Reset button. This will shut off the
engine immediately.
BEND THIS TAB TO CHANGE THE ENGINE SPEED (FREQUENCY).
STRETCHING SPRING INCREASES THE FREQUENCY (INCREASES ENGINE
SPEED).
RELAXING SPRING DECREASES THE FREQUENCY (DECREASES ENGINE SPEED).