Lp tank sizing, Lp/ng fuel conversion, Installing the battery – Winco ULPSS12H2W/E User Manual
Page 8
075-00
8
60706-209
Shown below is a diagram of a natural gas (NG)
installation.
Reference numbers 2 through 4 in the diagram
above are system parts supplied by the customer.
Reference number 4 is on the generator.
Below are tables of the fuel pressure readings at
each reference in the system.
FUEL PRESSURE TABLES
Single Low Pressure Regulator (LP Vapor only)
REF #
1
3
4
UNIT OFF
LINE PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
STARTING
LINE PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
NO LOAD
LINE PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
FULL
LOAD
LINE PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
Two (2) Regulator System (LP Vapor only)
REF #
1
2
3
4
UNIT
OFF
LINE PSI
10-15
LBS
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
START-
ING
LINE PSI
10-15
LBS
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
NO
LOAD
LINE PSI
10-15
LBS
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
FULL
LOAD
LINE PSI
10-15
LBS
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
Natural Gas
REF #
2
3
4
UNIT OFF
2 PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
STARTING
2 PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
NO LOAD
2 PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
FULL
LOAD
2 PSI
7-11 IN
4-6 OZ
7-11 IN
4-6 OZ
LP TANK SIZING
Required LP tank size for LP Vapor withdrawal
operating at various outside temperatures given in
degrees Fahrenheit (Celsius).
TANK TEMPERATURE
TANK SIZE
60° F (16° C)
150 GALLON
32° F (0° C)
250 GALLON
0° F (18° C)
500 GALLON
-20° F (-29° C)
1000 GALLON
LP/NG FUEL CONVERSION
The ULPSS2H2W/E generator sets have been
tested on
NATURAL GAS prior to shipment. If you
are going to use them on
LP vapor, follow the pro-
cedures in FUEL INSTALLATION. See Page 6.
INSTALLING THE BATTERY
**** CAUTION ****
In the following battery installation procedure, check
to be sure the selector switch remains in the “off”
position. This should be your last step before initial
start-up.
A customer supplied twelve-volt battery is required to
complete the installation. Installation of the high-
est CCA rated battery, within the correct BCI group
(size), will increase cold weather starting perfor-
mance. Gel batteries should not be used with the
battery tender installed in the generator enclosure.
Model Voltage BCI Group MINIMUM
CCA Rating
ULPSS12H2W 2 26 500
Installation and servicing of batteries must be per-
formed or supervised only by personnel knowledge-
able of batteries and the required precautions. Keep
unauthorized personnel away from batteries.