beautypg.com

Lp tank sizing, Lp/ng fuel conversion, Installing the battery – Winco ULPSS12H2W/E User Manual

Page 8

background image

075-00

8

60706-209

Shown below is a diagram of a natural gas (NG)

installation.

Reference numbers 2 through 4 in the diagram

above are system parts supplied by the customer.

Reference number 4 is on the generator.

Below are tables of the fuel pressure readings at

each reference in the system.

FUEL PRESSURE TABLES

Single Low Pressure Regulator (LP Vapor only)

REF #

1

3

4

UNIT OFF

LINE PSI

7-11 IN

4-6 OZ

7-11 IN

4-6 OZ

STARTING

LINE PSI

7-11 IN

4-6 OZ

7-11 IN

4-6 OZ

NO LOAD

LINE PSI

7-11 IN

4-6 OZ

7-11 IN

4-6 OZ

FULL

LOAD

LINE PSI

7-11 IN

4-6 OZ

7-11 IN

4-6 OZ

Two (2) Regulator System (LP Vapor only)

REF #

1

2

3

4

UNIT

OFF

LINE PSI

10-15

LBS

7-11 IN

4-6 OZ

7-11 IN

4-6 OZ

START-

ING

LINE PSI

10-15

LBS

7-11 IN

4-6 OZ

7-11 IN

4-6 OZ

NO

LOAD

LINE PSI

10-15

LBS

7-11 IN

4-6 OZ

7-11 IN

4-6 OZ

FULL

LOAD

LINE PSI

10-15

LBS

7-11 IN

4-6 OZ

7-11 IN

4-6 OZ

Natural Gas

REF #

2

3

4

UNIT OFF

2 PSI

7-11 IN

4-6 OZ

7-11 IN

4-6 OZ

STARTING

2 PSI

7-11 IN

4-6 OZ

7-11 IN

4-6 OZ

NO LOAD

2 PSI

7-11 IN

4-6 OZ

7-11 IN

4-6 OZ

FULL

LOAD

2 PSI

7-11 IN

4-6 OZ

7-11 IN

4-6 OZ

LP TANK SIZING

Required LP tank size for LP Vapor withdrawal

operating at various outside temperatures given in

degrees Fahrenheit (Celsius).

TANK TEMPERATURE

TANK SIZE

60° F (16° C)

150 GALLON

32° F (0° C)

250 GALLON

0° F (18° C)

500 GALLON

-20° F (-29° C)

1000 GALLON

LP/NG FUEL CONVERSION

The ULPSS2H2W/E generator sets have been

tested on

NATURAL GAS prior to shipment. If you

are going to use them on

LP vapor, follow the pro-

cedures in FUEL INSTALLATION. See Page 6.

INSTALLING THE BATTERY

**** CAUTION ****

In the following battery installation procedure, check

to be sure the selector switch remains in the “off”

position. This should be your last step before initial

start-up.

A customer supplied twelve-volt battery is required to

complete the installation. Installation of the high-

est CCA rated battery, within the correct BCI group

(size), will increase cold weather starting perfor-

mance. Gel batteries should not be used with the

battery tender installed in the generator enclosure.

Model Voltage BCI Group MINIMUM

CCA Rating

ULPSS12H2W 2 26 500

Installation and servicing of batteries must be per-

formed or supervised only by personnel knowledge-

able of batteries and the required precautions. Keep

unauthorized personnel away from batteries.