Initial start up, Start up procedure – Winco ULPSS12H2W/E User Manual

Page 13

background image

3

075-00

60706-209

WIRE #

PURPOSE

RECOMMENDED

COLOR

# 23

Start

Black

# 1

Battery Negative

White

Fuel line protected and a moisture trap in

stalled (may be required for NG).

LP/NG pressure OK. 4-6 oz. (7- in. WC).

Battery connections clean and tight.

Battery fully charged.

All AC and DC wiring installed and properly

protected.

LUBRICATON

Before starting the engine, check and fill the crank-

case with the proper weight/grade oil, as recom-

mended by the engine manufacturer’s maintenance

instructions. The necessity of using the correct oil,

and keeping the crankcase full cannot be over em-

phasized.

DO NOT OVERFILL THE ENGINE, Use

the dipstick.

After completing the above checklist, the generator

set is ready for the initial start-up test.

START UP PROCEDURE

Engine Generator Set only

The engine control module (ECM) is manufactured

by Deep Sea Electronics. Model 30 is used on

this engine generator set. See picture below. Ad-

ditional information on the DSE 30 is on pages 4

through 7.

Manual Operation

Press and release the red Stop/Reset button. Then

press and release the green Start Engine button.

The engine generator will crank and start automati-

cally. If the engine fails to start correct the problem

before proceeding.

With the engine running smoothly, check the no load

voltage and frequency at wire # and # 4 (L2 and

L6 in the ASCO ATS) on the generator terminal block

in the ATS. The voltage should be 240 volts plus or

minus nominal. The frequency should be between

6.5 to 62 hertz (Hz). The voltage should also be

checked between the hot terminals (L2 and L6) and

the neutral to be certain of a balanced voltage output

and a solid neutral connection. The voltage should

be about one half of the line to line voltage.

** NOTICE **

If for any reason during the check out procedures

the voltage and frequency are not correct, press the

Stop/Reset button and correct the trouble before

proceeding.

After verifying the voltage and frequency are correct,

press the Stop/Reset button. This will shut off the

engine immediately.

Transfer Switch & Engine Generator

Automatic (remote) Operation

This procedure checks the electrical operation of

the automatic transfer switch. If the actual operation

does not follow this procedure, consult the trou-

blshooting section in the transfer switch manual.

INITIAL START UP

******************

***** WARNING *****

******************

DO NOT jump start these generator sets. Starting

these units on a low battery of jump starting them

will cause damage to the engine control module.

Use the following checklist to verify correct in-

stallaion before starting the engine:

Engine oil. Check level & fill as required with

proper grade/quantity. Refer to engine owners

manual for proper levels and types.

Unit mounting base properly bolted down.

Clearance for service and maintenance on all

sides.

Proper fuel line material and size.

All fuel line connections tight.