Dse 3110 control fault codes – Winco ULPSS12H2W/E User Manual
Page 18
075-00
8
60706-209
DSE 3110 CONTROL
FAULT CODES
DESCRIPTION
AUXILIARY INPUTS
Auxiliary inputs can be user configured and will display
the message as written by the user.
FAIL TO START
The engine has not fired after the preset number of start
attempts
FAIL TO STOP
The module has detected a condition that indicates that
the engine is running when it has been instructed to stop.
NOTE:- ‘Fail to Stop’ could indicate a faulty oil pressure sensor
- If engine is at rest check oil sensor wiring and configuration.
LOW OIL PRESSURE
The module detects that the engine oil pressure has fallen
below the low oil pressure pre-alarm setting level after the
Safety On timer has expired.
ENGINE HIGH OIL
TEMPERATURE
The module detects that the engine oil temperature has
exceeded the high engine temperature pre-alarm setting
level after the Safety On timer has expired.
UNDERSPEED
The engine speed has fallen below the underspeed pre
alarm setting
OVERSPEED
The engine speed has risen above the overspeed pre
alarm setting
BATTERY UNDER
VOLTAGE / BATTERY
OVER VOLTAGE
The DC supply has fallen below or risen above the low/
high volts setting level.
GENERATOR UNDER
VOLTAGE
The generator output voltage has fallen below the pre-set
pre-alarm setting after the Safety On timer has expired.
GENERATOR OVER
VOLTAGE
The generator output voltage has risen above the pre-set
pre-alarm setting.
GENERATOR UNDER
FREQUENCY
The generator output frequency has fallen below the
pre-set pre-alarm setting after the Safety On timer has
expired.
GENERATOR OVER
FREQUENCY
The generator output frequency has risen above the pre-
set pre-alarm setting.
C
D