DSE 3110 CONTROL

FAULT CODES

DESCRIPTION

AUXILIARY INPUTS

Auxiliary inputs can be user configured and will display

the message as written by the user.

FAIL TO START

The engine has not fired after the preset number of start

attempts

FAIL TO STOP

The module has detected a condition that indicates that

the engine is running when it has been instructed to stop.

NOTE:- ‘Fail to Stop’ could indicate a faulty oil pressure sensor

- If engine is at rest check oil sensor wiring and configuration.

LOW OIL PRESSURE

The module detects that the engine oil pressure has fallen

below the low oil pressure pre-alarm setting level after the

Safety On timer has expired.

ENGINE HIGH OIL

TEMPERATURE

The module detects that the engine oil temperature has

exceeded the high engine temperature pre-alarm setting

level after the Safety On timer has expired.

UNDERSPEED

The engine speed has fallen below the underspeed pre

alarm setting

OVERSPEED

The engine speed has risen above the overspeed pre

alarm setting

BATTERY UNDER

VOLTAGE / BATTERY

OVER VOLTAGE

The DC supply has fallen below or risen above the low/

high volts setting level.

GENERATOR UNDER

VOLTAGE

The generator output voltage has fallen below the pre-set

pre-alarm setting after the Safety On timer has expired.

GENERATOR OVER

VOLTAGE

The generator output voltage has risen above the pre-set

pre-alarm setting.

GENERATOR UNDER

FREQUENCY

The generator output frequency has fallen below the

pre-set pre-alarm setting after the Safety On timer has

expired.

GENERATOR OVER

FREQUENCY

The generator output frequency has risen above the pre-

set pre-alarm setting.