Dse 3110 control – Winco ULPSS12H2W/E User Manual
Page 16
075-00
6
60706-209
DSE 3110 CONTROL
STOP/RESET (Red Button) This button places the module into its “Stop/
Reset” mode. This will clear any alarm conditions for which the triggering
criteria have been removed. If the engine is running and the module is in
Stop mode, the module will automatically instruct the changeover device to
unload the generator. (Close generator becomes inactive (if used)). The fuel
supply de-energizes and the engine comes to a standstill. Should a remote
start signal be present while operating in this mode, a remote start WILL NOT
occur.
AUTO (White Button) This button places the module into its “Automatic”
mode. This mode allows the module to control the function of the generator
automatically. The module will monitor the remote start input and once a start
request is made, the set will be automatically started and placed on load.
Upon removal of the starting signal, the module will automatically transfer the
load from the generator and shut the set down observing the stop delay timer
and cooling timer as necessary. The module will then wait the next start event.
START (Green button)
Pressing this button in auto mode will start the engine and run off load.
Pressing this button in Stop/Reset mode will turn on the CAN engine ECU
(when correctly configured and fitted to a compatible engine ECU).
PAGE
Pressing this button scrolls the display to show the various instruments.