**** CAUTION ****

These units are shipped with oil. Be sure to check

oil levels before operating. See engine manufactur-

er’s instruction manual for recommended oil require-

ments before initial starting.

UNPACKING

. Carefully remove the carton.

2. After inspecting the engine-generator and trans-

fer switch for external physical damage, check

for the following items packed inside the carton.

a. Owner’s manual.

b. Engine manufacturer’s instruction manual.

3. Remove main frame hold down bolts. (4)

4. Unit can now be lifted from shipping pallet.

INSTALLATION

General Information

******************

***** WARNING *****

******************

Before proceeding with the installation be sure the

operation selector switch is in the stop position.

These engine generator sets are designed to be

mounted on a concrete pad outdoors only. As an

option a prefab pad may be used as long as proper

attention is paid to site preparation to insure the unit

will not move after installation. The transfer switch is

mounted next to your electrical entrance or distribu-

tion panel inside or outside the building. Consult a

qualified, licensed electrician or contractor to install

and wire the transfer switch.

The installation must

comply with all national, state and local codes.

Before beginning the installation process check the

rating of the generator set and its transfer switch

rating. Be certain they can handle the intended

load and are compatible with the enterance voltage,

phase and current ratings. Plans for installation

should be prepared with proper attention to me-

chanical and electrical engineering detail to assure

a satisfactory system installation. The information

in this manual is offered only as a guide to finializing

your installation plans.

SPECIFICATIONS

GENERATOR

MODEL WATTS*

VOLTS AMPS HZ PH RPM

PSS2

2000

20/240

50.0

60

3600

* Derate 6% for Natural Gas operation. Derate to

792 watts when operating on Natural Gas pressure

of 4-6 inches water column. Derate 3.5% per 000

feet elevation above sea level.

FUEL CONSUMPTION

NATURAL GAS

1000 BTU/CU FT

LP VAPOR

2520 BTU/CU FT

CF/HR

190

76.6

BTU/HR

190,000

194,000

GAL/HR

N/A

2.1

LBS/HR*

N/A

9.0

* Based on full load operation.

ENGINE SPECIFICATIONS

Refer to engine operating and maintenance instruc-

tions.

** NOTICE **

When unpacking the generator set, be sure to in-

spect it carefully for freight loss or damage. If loss or

damage is noted at the time of delivery, require that

the person making the delivery make note of the loss

or damage on the freight bill, or affix his signature

under the consignor’s memo of the loss or damage.

Contact the carrier for claim procedures.

When loss or damage is noted after delivery, segre-

gate the damaged material, and contact the carrier

for claim procedures. Be sure to retain the packag-

ing material for carrier inspection.

“Concealed Damage” is understood to mean dam-

age to the contents of a package which is not evi-

dent at the time of delivery by the carrier, but wheich

is discovered later. The carrier or carriers are

responsible for merchandise lost or damaged in tran-

sit. The title to goods rests with the consignee when

generators are shipped F.O.B. factory, and only the

consignee can legally file a claim. Please note, most

carriers have a time limit for filing concealed damage

claims.