Dse 3110 engine control – Winco ULPSS12H2W/E User Manual
Page 15
5
075-00
60706-209
In order to set and test the exercise circuit the
engine control module must be set in the auto
mode.
SETTING THE EXERCISER CIRCUIT
Press and release the
Automatic Generator Exer-
ciser button. After about 8 seconds the exerciser
light flashes 4 times to indicate that the exerciser
circuit has been set. The number of flashes indi-
cates the number of days until the next exercise
period. This 20 minute period will occur at approxi-
mately the same time of the day the button was
pressed.
DISABLING THE EXERCISER CIRCUIT
Press and hold the
Automatic Generator Exerciser
button until the light goes off, the light flashes then
goes off.
ENABLING THE EXERCISER CIRCUIT
Press and hold the
Automatic Generator Exerciser
button until the light goes off, the light flashes then
goes off. After about 8 seconds the exerciser light
flashes fourteen times to indicate that the exerciser
circuit has be re-enabled.
******************
***** WARNING *****
******************
WITH A TOTAL POWER FAILURE (UTILITY
POWER FAILS AND THE GENERATOR FAILS TO
START AND RUN) THE EXERCISER MUST BE
RESET AFTER THE POWER IS RESTORED.
CLEARING AN “ERROR” CODE
An error codes occurs on the ASCO control board if
the generator set fails to start or there is some other
malfunction. BOTH Transfer Switch lights will be
blinking together. The Automatic Generator Exer-
ciser light will be blinking a number of times then
pause. This number gives the error code reason
from page 8 of the ASCO 65 owner’s manual. To
clear this code press and release the
Push to Test
button once. Then troubleshoot the problem accord-
ing to the ASCO 65 owner’s manual.
This completes your installation and unit testing.
ALWAYS leave the system in automatic mode unless
servicing the unit. For automatic operation, the auto
mode icon must be displayed on the engine control
module.
DSE 3110 ENGINE CONTROL
PROTECTIONS
When an alarm is present, the Common alarm LED
if configured will illuminate.
The LCD display will
show an icon to indicate the fault.
WARNINGS
Warnings are non-critical alarm conditions and do
not affect the operation of the generator system,
they serve to draw the operators attention to an un-
desireable condition. The icon will appear steady in
the display. Warning alarms are self-resetting when
the fault condition is removed.
SHUTDOWNS
Shutdowns are critical alarm conditions that stop the
engine and draw the operator’s attention to an un-
desirable condition. Shutdown alarms are latching.
The fault must be removed and the STOP/RESET
button pressed to reset the module. The icon will
appear flashing in the display.
MODULE DISPLAY
TIMER ICON
When the module is controlling the engine (start-
ing and stopping) an animated timer icon will be
displayed in the icon area to indicate that a timer is
active, for example cranking time, crank rest, etc.
STOPPED ICON
When there are no alarms present, an icon will be
displayed to indicate the engine is stopped and what
mode the unit is in.
Stop Mode Auto Mode Manual Mode
RUNNING ICON
When there are no alarms present, an animated icon
is displayed to indicate the engine is running.
USB ICON
When a USB connection is made to the module the
USB icon is displayed.
MEMORY CORRUPTION
If either the config file or engine file becomes cor-
rupted the unit will display the following icon.