5

075-00

60706-209

In order to set and test the exercise circuit the

engine control module must be set in the auto

mode.

SETTING THE EXERCISER CIRCUIT

Press and release the

Automatic Generator Exer-

ciser button. After about 8 seconds the exerciser

light flashes 4 times to indicate that the exerciser

circuit has been set. The number of flashes indi-

cates the number of days until the next exercise

period. This 20 minute period will occur at approxi-

mately the same time of the day the button was

pressed.

DISABLING THE EXERCISER CIRCUIT

Press and hold the

Automatic Generator Exerciser

button until the light goes off, the light flashes then

goes off.

ENABLING THE EXERCISER CIRCUIT

Press and hold the

Automatic Generator Exerciser

button until the light goes off, the light flashes then

goes off. After about 8 seconds the exerciser light

flashes fourteen times to indicate that the exerciser

circuit has be re-enabled.

******************

***** WARNING *****

******************

WITH A TOTAL POWER FAILURE (UTILITY

POWER FAILS AND THE GENERATOR FAILS TO

START AND RUN) THE EXERCISER MUST BE

RESET AFTER THE POWER IS RESTORED.

CLEARING AN “ERROR” CODE

An error codes occurs on the ASCO control board if

the generator set fails to start or there is some other

malfunction. BOTH Transfer Switch lights will be

blinking together. The Automatic Generator Exer-

ciser light will be blinking a number of times then

pause. This number gives the error code reason

from page 8 of the ASCO 65 owner’s manual. To

clear this code press and release the

Push to Test

button once. Then troubleshoot the problem accord-

ing to the ASCO 65 owner’s manual.

This completes your installation and unit testing.

ALWAYS leave the system in automatic mode unless

servicing the unit. For automatic operation, the auto

mode icon must be displayed on the engine control

module.

DSE 3110 ENGINE CONTROL

PROTECTIONS

When an alarm is present, the Common alarm LED

if configured will illuminate.

The LCD display will

show an icon to indicate the fault.

WARNINGS

Warnings are non-critical alarm conditions and do

not affect the operation of the generator system,

they serve to draw the operators attention to an un-

desireable condition. The icon will appear steady in

the display. Warning alarms are self-resetting when

the fault condition is removed.

SHUTDOWNS

Shutdowns are critical alarm conditions that stop the

engine and draw the operator’s attention to an un-

desirable condition. Shutdown alarms are latching.

The fault must be removed and the STOP/RESET

button pressed to reset the module. The icon will

appear flashing in the display.

MODULE DISPLAY

TIMER ICON

When the module is controlling the engine (start-

ing and stopping) an animated timer icon will be

displayed in the icon area to indicate that a timer is

active, for example cranking time, crank rest, etc.

STOPPED ICON

When there are no alarms present, an icon will be

displayed to indicate the engine is stopped and what

mode the unit is in.

Stop Mode Auto Mode Manual Mode

RUNNING ICON

When there are no alarms present, an animated icon

is displayed to indicate the engine is running.

USB ICON

When a USB connection is made to the module the

USB icon is displayed.

MEMORY CORRUPTION

If either the config file or engine file becomes cor-

rupted the unit will display the following icon.