Viconics R850 Installation Guide User Manual

Innovative control solutions for your needs, R850v-8, R850v-4

background image

R850 SERIES

R850V STEP CONTROLLER

WITH INTEGRATED VERNIER STAGE

Pulsed or analog 0 to 10 Vdc vernier stage

4 or 8 step models

Up to 16 stage total with a slave unit

Test button

DESCRIPTION
The Viconics R850V series step controller is designed for
cost effective, precise modulation of multi-stage control
application. A common application is a multi step electric
duct heater.
An integrated vernier control output will give a precise and
full modulation of the load from 0 to 100% of the total
capacity.

FEATURES AND BENEFITS
Microcomputer-based design

Accuracy and reliability

Adjustable inter-stage delay

Provides flexibility in
replacement applications

Adjustable Vernier ratio

Simplifies design of
proportional stage

Choice of pulsed or analog
Vernier output

Permits use of SCR or lower
cost SSR

Up to 16 stages

One product family can handle
all applications

Choice of LIFO or FIFO
sequencing

Increased flexibility of FIFO
permits even use of contactors

Test button

Quick troubleshooting

MODELS AVAILABLE
The R850-V is available in 2 models

R850V-4

4 stage unit

R850V-8

8 stage unit

If more than 8 stage are required, the R850-V8 can be used
as a master unit with another R850V as a slave unit. Adding
another unit ( R850-V4 or R850-V8 ) can bring the total step
number up to 12 or 16.

OVERRIDE TEST BUTTON

The override test button can be used to by-pass the
interstage delay and bring on all stage at one time. This
simplifies the verification of configured maximum number of
stage.

A status LED per step will come on for each of the configured
stage.

SPECIFICATIONS

Operating

Conditions:

0°C to 80°C ( 32°F to 176°F )
0 % to 95 % R.H. non-condensing

Relay outputs:

Isolated relay 30 Vac @ 1.0 amps. max. per
output, up to a maximum of 4.0 amps. total
per R850 controller. See application note 02.

Vernier stage:

Vdc pulsed: 6 Vdc, 30 mA max.
0 to 10 Vdc 5 mA max.

Input

impedance:

0 to 10 Vdc into 10 K

Ω minimum

Power supply:

24 Vac -15%, +10% 50/60 Hz; 4 VA

Use a Class 1 ( properly fused ) or Class 2,
CSA or UL recognized transformer for power
supply & relay outputs.

Specifications and equipment are subject to change without prior notice.

INPUT SIGNAL
The R850V has four INPUT dip switch (S1 to S4) to select the control signal input:
They are compatible with industry standard signals.

DIP SWITCH ADJUSTMENTS & WIRING CONTROL INPUT

Input Signal Switch

Switch #1

Switch #2

Switch #3

Switch #4

0 to 10 Vdc control signal ( 2 to 10 Vdc control range )

Off

Off

Off

On

4 to 20 mA control signal

Off

Off

On

Off

0 to 135

Ω control signal

On

On

Off

Off

If a slave unit is used, wire the control signal input to the master unit only

Innovative Control Solutions For Your Needs

(2) Vernier stage selection
OFF = 0 to 10 Vdc (SCR)
ON = Vdc pulsed signal (SSR)

4 to 20 mA

0 to 135

2

1

3 4

ON

2

1

3 4

(1) Sequence of operation

(LIFO or FIFO)
OFF = LIFO (Last IN, First OUT)
ON = FIFO (First IN, First OUT)

R850V-8

0 to 10 Vdc

signal selection

(1-4) Input

ON

2

1

3 4

ON

I

N

P

U

T

2

1

4

3

S

ON

1
W

(3-6) Number of steps selection
(see next pages for details)

C

O

N

T

R

O

L

4

2

1

3

5 6

S

ON

2
W

4 to 20 mA

(2) Vernier stage selection
OFF = 0 to 10 Vdc (SCR)
ON = Vdc pulsed signal (SSR)
(1) Sequence of operation

(LIFO or FIFO)

OFF = LIFO (Last IN, First OUT)
ON = FIFO (First IN, First OUT)

0 to 135

1 2 3 4

ON

1

3

2

4

2
W

S

(3-4) Number of steps selection
(see next pages for details)

S

signal selection

(1-4) Input

0 to 10 Vdc

ON

1

3

2

4

ON

I

N

P

U

T

1

3

2

44

C

O

N

T

R

O

L

3

1 22

4

W1

R850V-4

ON

ON