The damper position is never linear or proportional to airflow in a pressure dependent application.
Depending on how the zone damper was sized, a box may best slightly oversized, or slightly
undersized. In all cases, the PI loop (Proportional Integral) of the zone controller will always
compensate to find the proper required position to satisfy the current zone demand.

% opening

Air flow

% opening

Air flow

Oversized VAV

Undersized VAV

Effective

Control

Area

Effective

Control

Area

-

Be sure the VAV actuator is properly installed and set-up so the VAV damper blade is able to
rotate from the fully opened, to fully closed position with no restriction to its mechanical rotation.










2F) Terminal Reheat Lockout


It is possible to lockout out the local terminal reheat function of the zones during hot seasons or when no
longer required. This prevents users from using the local reheat function simply based on a configured
outside air temperature value.

If RehtConf is set to

AO2 OALK

BO5 OALK

0 = None

N/A, reheat not used

N/A, reheat not used

1 = Analog Duct Reheat Only

Set to desired value

N/A BO5 not used by this reheat
sequence

2 = On/Off Duct Reheat Only

N/A AO2 not used by this reheat
sequence

Set to desired value

3 = On/Off Perimeter Reheat Only N/A AO2 not used by this reheat

sequence

Set to desired value

4 = Analog Duct Reheat & On/Off
Perimeter Reheat

Set to desired value. Can be
different than BO5 OALK

Set to desired value. Can be
different than AO2 OALK