25 | PIR Ready VT7200 Series-Installation Guide
Set Type
Temporary setpoint
enable
Default is : Permnent
Enables temporary
setpoints feature to any
change of occupied or
unoccupied setpoint.
Temporar: (temporary) Local changes to the heating or cooling
setpoints by the user are temporary. They will remain effective
for the duration specified by
“ToccTime”. Setpoints will then
revert back to their default value after internal timer
“ToccTime”
expires.
To change setpoints permanently, revert this variable to No or
write setpoints through the network. Any setpoints written
through the network will be permanent and saved to EEPROM.
Permnent: (permanent) Any change of occupied or unoccupied
setpoints through the keypad by the user are permanent and
saved to & EEPROM
TOccTime
Temporary occupancy
time
Default value = 2 hours
Temporary occupancy time with occupied mode setpoints when
override function is enabled.
When the Terminal Equipment Controller is in unoccupied
mode, function is enabled with either the menu or UI2
configured as remote override input.
Range is: 0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, & up to 24 hours
Deadband
Minimum deadband
Default value = 2.0 °F
( 1.0 °C )
The minimum deadband value between the heating and cooling
setpoints. When modified, it will take effect only when any of
the setpoints are modified again.
Range is: 2, 3, 4 or 5 °F, 1.0 °F increments ( 1.0 to 2.5 °C, 0.5
°C increments )
Cal RS
Room temperature
sensor calibration
Default value =
0.0 °F or °C
Offset that can be added/subtracted to the actual displayed
room temperature
Range is: ± 5.0 °F, 1.0 °F increments ( ± 2.5 °C, 0.5 °C
increments )