E) Fan mode setting

Fan mode
set Y/N

This section of the menu is permits the setting of the fan mode operation.

Use ▲▼ to set value, Yes key to confirm

Fan mode
On

On fan mode
Fan is on continuously, even when system mode is OFF.

Fan mode
Auto

Automatic fan mode
Fan cycles on a call for heating or cooling for both occupied & unoccupied periods.

Fan mode
Smart

Smart fan mode
During occupied periods, fan is on continuously. In unoccupied mode, fan cycles on a call for heating or cooling.
This selection is available on all models with a communication module, on all stand-alone programmable models
or if DI1 or DI2 is set to RemNSB on stand-alone non-programmable models

F) Schedule

set (2 events)

Scheduling can have 2 or 4 events per day. This is set in the configuration menu as per parameter (2/4event )

Schedule
set Y/N

This section of the menu permits the user to set the whether 2 or 4 events is needed. Each day can be tailored to specific schedules
if needed.
• 2 events can be programmed per day.
• Occupied & unoccupied periods can be set for each day.

Monday timer

Schedule set

Tuesday timer

Schedule set

Wednesday timer

Schedule set

Other days are identical

Monday
set? Y/N

No next

Yes down

Tuesday
set? Y/N

No next

Yes down

Wednesda
set? Y/N

No next

Yes down

Selects the day to be programmed or
modified

Yes key to access day scheduling, No key to jump to next day

Occupied
Day? Y/N

No next

Yes down

Occupied
Day? Y/N

No next

Yes down

Occupied
Day? Y/N

No next

Yes down

Yes = Daily schedules will be accessed
No = Unoccupied mode all day

Yes key to access day scheduling, No key to jump to next day

Copy Y/N
Previous

Yes next

No down

Copy Y/N
Previous

Yes next

No down

Yes = Will copy previous day schedule
No = Daily schedules will be accessed

Yes key to copy previous day, No key to set new time value for each day

Occupied
00:00 AM

Use ▲▼
To set value

Occupied
00:00 AM

Use ▲▼
To set value

Occupied
00:00 AM

Use ▲▼
To set value

Sets Event # 1 Occupied time
Will activate occupied setpoints

Use ▲▼ to set value, Yes key to confirm

Unoccup
00:00 AM

Use ▲▼
To set value

Unoccup
00:00 AM

Use ▲▼
To set value

Unoccup
00:00 AM

Use ▲▼
To set value

Sets Event # 2 Unoccupied time
Will activate unoccupied setpoints

Use ▲▼ to set value, Yes key to confirm

Typical examples of a 2 event office schedule
Ex. #1 Office building closed all weekend

Event

Period #1 - Event #1

Period #1 - Event #2

Occupied

Unoccupied

Cool Heat Cool Heat

Daily

Setpoint

72 °F

70 °F

80 °F

62 °F

Occupancy

Monday

7.00 AM

6.00 PM

Day time only

Tuesday

7.00 AM

6.00 PM

Day time only

Wednesday

7.00 AM

6.00 PM

Day time only

Thursday

7.00 AM

6.00 PM

Day time only

Friday

7.00 AM

6.00 PM

Day time only

Saturday

12.00 PM *

12.00 PM *

Unoccupied

Sunday

12.00 PM *

12.00 PM *

Unoccupied

* Programming consecutive events to the same time will cause the thermostat to choose the last event as the time at which it will set

its schedule. In the above example, the thermostat will control to the unoccupied set point until 7:00 AM Monday.

Ex. #2 Commercial building which is occupied all weekend

Event

Period #1 - Event #1

Period #1 - Event #2

Occupied

Unoccupied

Cool Heat Cool Heat

Daily

Setpoint

72 °F

70 °F

80 °F

62 °F

Occupancy

Monday

8.00 AM

5.00 PM

Day time only

Tuesday

8.00 AM

5.00 PM

Day time only

Wednesday

8.00 AM

5.00 PM

Day time only

Thursday

8.00 AM

5.00 PM

Day time only

Friday

8.00 AM

5.00 PM

Day time only

Saturday

12.00 AM **

11.59 PM **

Occupied

Sunday

12.00 AM **

11.59 PM **

Occupied