Sequence of operation – Viconics VT7000 Series Application Guide User Manual

Page 8

background image

8

1) VT7300 Stand-alone fan coil application using 3 levels of occupancy with a VI-PIR accessory cover

Set-up and Configuration

Thermostat used

VT73x0X5000 ( commercial models )

PIR used

COV-PIR-FCU-C-5000 accessory cover

BI2 Configuration

None, no function

Stand-by timer value

2.0 hours

Unoccupied timer value

6.0 hours

Network interface used

None, stand-alone

Sequence of operation:

At initial power-up, when the thermostat 24 Vac power supply is applied; the initial occupancy of the zone will be stand-by
mode if the PIR device do not detect any movements.

As soon as the PIR device detects a movement or motion, the occupancy status switches to occupied and the occupied
setpoints are used.

Anytime the PIR device detects local motion, the elapsed stand-by timer value will be reset. If no motion is detected in the
zone for the entire stand-by timer duration, then the room switches to stand-by mode and the stand-by setpoints are used.

While in stand-by mode, if no motion is detected in the zone for the entire unoccupied timer duration, then the room switches
to unoccupied mode and the unoccupied setpoints are used.

At anytime, if the PIR device detects a local movement or motion, the occupancy status switches to occupied and the
occupied setpoints are used.

2) VT7300 Stand-alone fan coil application using 2 levels of occupancy with a VI-PIR accessory cover

Set-up and Configuration

Thermostat used

VT73x0X5000 ( commercial models )

PIR used

COV-PIR-FCU-C-5000 accessory cover

BI2 Configuration

None, no function

Stand-by timer value

2.0 hours

Unoccupied timer value

0.0 hours

Network interface used

None, stand-alone

Sequence of operation:


At initial power-up, when the thermostat 24 Vac power supply is applied; the initial occupancy of the zone will be stand-by
mode if the PIR device do not detect any movements.

As soon as the PIR device detects a movement or motion, the occupancy status switches to occupied and the occupied
setpoints are used.

Anytime the PIR device detects local motion, the elapsed stand-by timer value will be reset. If no motion is detected in the
zone for the entire stand-by timer duration, then the room switches to stand-by mode and the stand-by setpoints are used.

At anytime, if the PIR device detects a local movement or motion, the occupancy status switches to occupied and the
occupied setpoints are used.

The local zone never goes into unoccupied mode and the unoccupied setpoints are never used.

Unoccupied Time

= 6 Hours

Stand-By Time

= 2 Hours

First Movement Detected

by the PIR Cover

Occupied

Stand-By

Unoccupîed

Time

Stand-By Time Elapsed
= Stand-By Mode

Unoccupied Time Elapsed
= Unoccupied Mode

Initial State at

Power-Up = Stand-By

Unoccupied Time

= 0 Hours

Stand-By Time

= 2 Hours

Occupied

Stand-By

Unoccupîed

Time

Stand-By Time Elapsed
= Stand-By Mode

Last Movement Detected

by PIR Activity

Time

Stand-By Time Elapsed
= Stand-By Mode

Stand-By Time

= 2 Hours

Unoccupied Time

= 0 Hours

First Movement Detected

by the PIR Cover

Initial State at

Power-Up = Stand-By