VI-PIR Cover Installation

Remove security screw on the bottom of the current thermostat cover.

Open up by pulling on the bottom side of thermostat. (Fig. 3)


A)

Identify current thermostat model type:

Use appropriate cover accessory part number as identified on the first page by referring to the thermostat model
number

The male polarized PIR connector is located at bottom left corner of thermostat (Fig. 4)


B) Installation:

Hinge new PIR thermostat cover into position (fig. 3).

Insert polarized connector into PIR female connector located on thermostat base (Fig 4)

Snap PIR thermostat cover into place and re-install the security screw

Make appropriate parameter settings related to your application within the configuration menu as identified in the
thermostat installation

Electronic controls are static sensitive devices. Discharge yourself properly before manipulation and
installing the thermostat and its accessories.

Short circuit or wrong wiring may permanently damage the thermostat or the equipment.

All VT7000 series thermostats are to be used only as operating controls. Whenever a control failure could
lead to personal injury and/or loss of property, it becomes the responsibility of the user to add safety
devices and/or alarm system to protect against such catastrophic failures.


Specifications

PIR cover power requirements:

5 Vdc Max current draw of 7mA

Operating conditions: 0 °C to 50 °C ( 32 °F to 122 °F )

0% to 95% R.H. non-condensing

Storage conditions: -30 °C to 50 °C ( -22 °F to 122 °F )

0% to 95% R.H. non-condensing

Sensor:

Local Passive Infra Red Sensor

Dimensions with Thermostat:

4.94” x 3.38” x 1.13”

Approximate shipping weight with Thermostat:

0.75 lb ( 0.34 kg )

Agency Approvals:

UL

UL 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN
XAPX (US) and XAPX7 (Canada)

FCC

Compliant to CFR 47, Part 15, Subpart B, Class A (US)

Industry Canada

ICES-003 (Canada)

CE

EMC Directive 89/336/EEC (Europe Union)

C-Tick

AS/NZS CISPR 22 Compliant (Australia / New Zealand)
Supplier Code Number N10696


Drawing & Dimensions





























Thermostat Dimensions

Fig.5

Fig.4

Fig.3