Viconics VT7000 Series Application Guide User Manual
Page 6

6
•
Initial State, PIR Occupancy Routine: The initial effective occupancy state on power-up with either a PIR cover is
present or one of the inputs is configured for a remote PIR sensor is always Stand-By mode.
When the network effectively releases a thermostat to its local PIR routine from a previous occupied or unoccupied
network state, the resulting occupancy state is always Stand-By mode.
Initial Power-Up, Stand-Alone or Networked
After Receiving the Local Occupancy / PIR Network Command From a Previous Unoccupied State
After Receiving the Local Occupancy / PIR Network Command From a Previous Occupied State
Unoccupied Time
= 6 Hours
Stand-By Time
= 2 Hours
First Movement Detected
by the PIR Cover
Occupied
Stand-By
Unoccupîed
Time
Stand-By Time Elapsed
= Stand-By Mode
Unoccupied Time Elapsed
= Unoccupied Mode
Initial State at
Power-Up = Stand-By
Unoccupied Time
= 6 Hours
Stand-By Time
= 2 Hours
First Movement Detected
by the PIR Cover
Occupied
Stand-By
Unoccupîed
Time
Stand-By Time Elapsed
= Stand-By Mode
Unoccupied Time Elapsed
= Unoccupied Mode
Initial State at
Local Occupancy
Network Command
= Stand-By
Current Network
Command = Unoccupied
Unoccupied Time
= 6 Hours
Stand-By Time
= 2 Hours
First Movement Detected
by the PIR Cover
Occupied
Stand-By
Unoccupîed
Time
Stand-By Time Elapsed
= Stand-By Mode
Unoccupied Time Elapsed
= Unoccupied Mode
Initial State at
Local Occupancy
Network Command
= Stand-By
Current Network
Command = Occupied