15) VT7300 Stand-alone fan coil application using 3 levels of occupancy with a remote PIR sensor

Set-up and Configuration

Thermostat used

VT73x5X5000 ( lodging models )

PIR used

BI1 configured for remote PIR sensor

BI2 Configuration

Door dry contact

Stand-by timer value

Not used

Unoccupied timer value

6.0 hours

Network interface used

None, stand-alone


Sequence of operation:

At initial power-up, when the thermostat 24 Vac power supply is applied; the initial occupancy of the zone will be stand-by
mode if the PIR device do not detect any movements.

As soon as the PIR device detects a movement or motion, the occupancy status switches to occupied and the occupied
setpoints are used. The room will then be in occupied mode until a door toggle is detected.

If a door toggle is detected, then the room switches to stand-by mode and the stand-by setpoints are used. If any occupants
are left in the room, local movements must be seen to resume the occupied mode.

While in stand-by mode, if no motion is detected in the zone for the entire unoccupied timer duration, then the room switches
to unoccupied mode and the unoccupied setpoints are used.

At anytime, if the PIR device detects a local movement or motion, the occupancy status switches to occupied and the
occupied setpoints are used.

16) VT7300 Stand-alone fan coil application using 2 levels of occupancy with a remote PIR sensor

Set-up and Configuration

Thermostat used

VT73x5X5000 ( lodging models )

PIR used

BI1 configured for remote PIR sensor

BI2 Configuration

Door dry contact

Stand-by timer value

Not used

Unoccupied timer value

0.0 hours

Network interface used

None, stand-alone


Sequence of operation:

t initial power-up, when the thermostat 24 Vac power supply is applied; the initial occupancy of the zone will be stand-by mode
if the PIR device do not detect any movements.

As soon as the PIR device detects a movement or motion, the occupancy status switches to occupied and the occupied
setpoints are used. The room will then be in occupied mode until a door toggle is detected.

If a door toggle is detected, then the room switches to stand-by mode and the stand-by setpoints are used. If any occupants
are left in the room, local movements must be seen to resume the occupied mode.

At anytime, if the PIR device detects a local movement or motion, the occupancy status switches to occupied and the
occupied setpoints are used.

The local zone never goes into unoccupied mode and the unoccupied setpoints are never used.

Remote PIR Sensor

Door Switch

Remote PIR Sensor

Door Switch

Unoccupied Time

= 6 Hours

Occupied

Stand-By

Unoccupîed

Time

Unoccupied Time Elapsed
= Unoccupied Mode

Initial State at

Power-Up = Stand-By

Always

Occupied

Door Open/Close
Toggle Detected

Unoccupied Time

= 0 Hours

Occupied

Stand-By

Unoccupîed

Time

Last Movement Detected

by PIR Activity

Time

Unoccupied Time

= 0 Hours

First Movement Detected

by a PIR Device

Initial State at

Power-Up = Stand-By

Always

Occupied

Always

Occupied

Door Open/Close
Toggle Detected

Door Open/Close
Toggle Detected