RTF/HIB Torque Requirements (in-lb)
FAN
NESTED INLET VANES
EXTERNAL INLET VANES
SIZE
CL 18/20
CL 23/24
CL 18/20
CL 23/24
180
N/A
N/A
190
310
200
N/A
N/A
230
370
220
N/A
N/A
280
460
240
N/A
N/A
340
550
270
390
640
410
670
300
480
780
500
820
330
580
950
610
1000
360
710
1170
750
1230
400
870
1430
920
1490
450
1060
1740
1120
1820
490
1290
2120
1360
2920
540
1580
2590
1670
3570
600
1930
3830
2690
4370
660
2810
4630
3250
5290
730
3430
5650
3970
6460
800
4200
6920
4860
7910
Industrial Torque Requirements (in-lb)
FAN
EXTERNAL INLET VANES
SIZE
CL 18/20
CL 23/24
CL 18/20
913
120
170
240
915
170
230
330
917
210
290
420
919
260
360
520
921
320
440
630
923
390
530
760
926
490
680
970
929
620
850
1220
933
800
1100
1580
937
1000
1380
1970
941
1230
1690
3180
945
1480
2680
3840
949
2320
3180
4560
954
2800
3840
5510
960
3470
4750
6810
NOTES:
1. Standard length of the handle supplied by Twin City Fan is
10". The force required to operate inlet vane is:
Torque in In-Lb
Length of Lever
2. For sizing actuator, multiply above torque by 1.2 for rotary and
1.5 for linear actuators.
Twin ciTy fan & blower | www.Tcf.com
5959 Trenton Lane N | Minneapolis, MN 55442 | Phone: 763-551-7600 | Fax: 763-551-7601