Toa FS-970 SERIES User Manual
Page 51

51
24 V IN, M4 screw terminal
24 V OUT, M4 screw terminal
Emergency DS activation output: 24 VDC, 0.1 A, M4 screw terminal
Emergency DS control input: 24 VDC, 5 A, M4 screw terminal
Battery check output (up to 50 DS-029Bs connectable):
Open collector output, rated voltage: 30 VDC,
current capacity: 0.5 A, M4 screw terminal
Battery fail input: Open voltage: 24 VDC, short-circuit current: 5 mA,
M4 screw terminal
Emergency cut-off 24 V: 24 VDC, 0.5 A, M3.5 screw terminal
24 V in emergency:
24 VDC, 0.1 A, M4 screw terminal
EB 1 and 2:
Relay output, contact rating: 30 VDC, 1 A,
M3.5 screw terminal
Emergency contact:
Relay output, contact rating: 30 VDC, 1 A,
M3.5 screw terminal
Remote control:
Relay output, contact rating: 30 VDC, 1 A,
M3.5 screw terminal
General DS start:
M4 screw terminal
Timer 1 and 2:
Open voltage: 24 VDC, short circuit current: 5 mA,
M3.5 screw terminal (Timer 1), M4 screw terminal (Timer 2)
PA fail:
Open voltage: 24 VDC, short circuit current: 5 mA,
M4 screw terminal
Attenuator-free control, power failure control: Open voltage: 24 VDC,
short circuit current: 200 mA,
M3.5 screw terminal (power failure control),
M4 screw terminal (attenuator-free control)
General DS control: M4 screw terminal
SWITCHED:
3 outlets (up to 820 VA per outlet)
UNSWITCHED: 2 outlets (total up to 450 VA)
Panel: Zinc-plated steel plate, 1mm thick, black paint
Case: Zinc-plated steel plate, 1 mm thick
482 (w) x 177 (h) x 328.3 (d) mm
10.6 kg
ø5 mm miniature tube fuse: 0.5 A x 4, 1.6 A x 2, 1 A x 1, 3 A x 1,
JP-EP control connector cable x 1, JP-EP power connector cable x 1,
rack mounting screw x 4
Power Connection
Section
Input
Output
Control
External Control Output
External Control Input
AC Power Output
Finish
Dimensions
Weight
Accessories