Carrier 50JZ 024-060 User Manual
Page 25
Table 13—48GP & 48JZ Gas Heating ICM Airflow
Small Cabinet
EASY SELECT™
BOARD SETTING (CFM)
700
800
1100
1250
Unit
Size
External
Static
Pressure
0.0–0.4
0.4–0.7
0.7–1.0
0.0–0.4
0.4–0.7
0.7–1.0
0.0–0.4
0.4–0.7
0.7–1.0
0.0–0.4
0.4–0.7
0.7–1.0
Gas Heat Size
024
040
–
–
–
855
770
710
–
–
–
–
–
–
060
–
–
–
–
–
–
1020
890
835
–
–
–
030
040
–
–
–
880
840
805
–
–
–
–
–
–
060
–
–
–
–
–
–
1030
970
910
–
–
–
036
060
–
–
–
–
–
–
1035
995
955
–
–
–
090
–
–
–
–
–
–
–
–
–
1170
1110
1025
Table 14—48GP & 48JZ Gas Heating ICM Airflow
Large Cabinet
EASY SELECT™
BOARD SETTING (CFM)
1000
1250
1600
1750
1800
Unit
Size
External
Static
Pressure
0.0–1.0
0.0–1.0
0.0–1.0
0.0–1.0
0.0–1.0
Gas Heat Size
042
060
1000
–
–
–
–
090
–
1250
–
–
–
048
090
–
1250
–
–
–
115
–
–
1600
–
–
130
–
–
–
1750
–
060
090
–
1250
–
–
–
115
–
–
1600
–
–
130
–
–
–
–
1800
Table 15—48GP & 48JZ ICM Air Flow vs. Temperature Rise Chart
UNIT
COOLING
SIZE
RATED GAS
INPUT RATE
(X 1000)
AIRFLOW SETTING
EASY SELECT™
(SCFM)
CALCULATED
TEMPERATURE
RISE
MIN.
TEMP
RISE
MAX
TEMP
RISE
MAX
DISCH.
TEMP
48GP
&
48JZ
024
40
800
36.5
20
50
175
60
(48GP Only)
1100
40
35
65
165
030
40
800
36.5
20
50
175
60
1100
40
35
65
165
036
60
1100
40
25
55
165
90
1200
54
45
75
175
042
60
1000
44
20
50
165
90
1250
53
35
65
170
048
90
1250
53
25
55
165
115
1600
53
35
65
170
130
1750
54
40
70
175
060
90
1600
41
25
55
155
115
1600
53
35
65
170
130
1800
53
40
70
175
25