Inj . pump 6.00, St ar t aut ocal, St ar t 235 p – TeeJet 026 – 73 AddFlow User Manual
Page 7: Inj . vol 0.000 l, Pr ime, 000 l, Pr iming 0.000 l
7. Pump
autocalibration
Function
Display
Possible actions
Comments
2.2 Injection
pump
calibration
Inj . pump
6.00
↑ ↓ to modify value
Pro to validate value (2)
This is the complete
pump calibration (all
heads together.
Units are pulses/ml.
CLR to start Autocalibration
Average value is 3.00 per
head for a piston pump.
2.2.1
St ar t
aut ocal
CLR to exit Autocalibration
Push on the CAL switch on the pump to
start the calibration.
Collect the pumped volume.
Keep the CAL switch pushed until
calibration is finished
Pump must be ready to
inject (tubes filled)
2.2.2
St ar t
235 p
Display shows the counted pulses from
the pump.
Release the CAL switch
when enough pulses
have been counted.
2.2.3
inj . vol
0.000 l
↑ ↓ to set the pumped volume
Pro to validate
Release the CAL switch
when enough pulses
have been counted.
8. Prime
autocalibration
Function
Display
Possible actions
Comments
↑ ↓ to modify value
This is the volume that
must be pumped to prime
the system.
3.1 Prime
calibration
Pr ime
2.000 l
Pro to validate value
CLR to start Autocalibration
Push on the CAL switch on the pump to
start the calibration.
2.2.1
St ar t
aut ocal
Keep the CAL switch pushed until
calibration is finished
Display will show injected volume
2.2.1
pr iming
0.000 l
Release the CAL switch when system
has been primed
Pro to validate
026-UK V1.01
18/05/2006