SC-3 Controller

18

Advanced / Installer

The Adv / Installer DIP switch selects the access level of the control. In the

Installer access level, a limited number of items may be viewed and / or

adjusted. In the Advanced access level, all items may be viewed and / or

adjusted.

Set to Advanced

Rotate / Off

The Rotate / Off DIP switch selects whether or not the control is to provide

Equal Run Time Rotation of the boiler stages. If the switch is set to Rotate,

the stages will be rotated accordingly. If the switch is set to Off, the firing

sequence is fixed starting with the module 1 to module 3.

We recommend that it be set to Rotate for most
systems.

Off/Exercise

The Off / Exercise DIP switch selects whether or not the control is to exercise

the primary pump and boiler pumps. If the DIP switch is set to Exercise, the

pumps are operated for 10 seconds after every three days of inactivity.

We recommend that it be set to Exercise for most
systems.

THE CONTROL MUST BE ADJUSTED FOR YOUR APPLICATION.

IF ANY OF THE DEFAULT SETTINGS DO NOT SUIT YOUR APPLICATION,

GO TO THE ADJUSTING SECTION THAT FOLLOWS EACH FUNCTION

AND WRITE IN THE DESIRED SETTING IN THE SQUARE BOX PROVIDED

FOR THAT FUNCTION. THEN PERFORM THE ADJUSTMENT AS LISTED.

IT IS BEST IF YOU TAKE A FEW MINUTES TO GO THROUGH THE ENTIRE LIST OF FUNCTIONS AND

ENTER ANY NEW SETTINGS THAT ARE APPROPRIATE FOR YOUR INSTALLATION

.

WHEN FINISHED

,

GO TO THE CONTROL AND ADJUST ONLY THOSE FUNCTIONS THAT HAVE A NEW SETTING LISTED

.

SPACE HEATING ONLY WITH SETPOINT CONTROL