SC-3 Controller

SPACE HEATING ONLY WITH OUTDOOR RESET

Advanced / Installer

The Adv / Installer DIP switch selects the access level of the control. In the

Installer access level, a limited number of items may be viewed and / or

adjusted. In the Advanced access level, all items may be viewed and / or

adjusted.

Set to Advanced

Rotate / Off

The Rotate / Off DIP switch selects whether or not the control is to provide

Equal Run Time Rotation of the boiler stages. If the switch is set to Rotate,

the stages will be rotated accordingly. If the switch is set to Off, the firing

sequence is fixed starting with the module 1 to module 3.

We recommend that it be set to Rotate for most systems

Off / Exercise

The Off / Exercise DIP switch selects whether or not the control is to exer-

cise the primary pump and boiler pumps. If the DIP switch is set to Exercise,

the pumps are operated for 10 seconds after every three days of inactivity.

We recommend that it be set to Exercise for most systems.

THE CONTROL MUST BE ADJUSTED FOR YOUR APPLICATION.

IF ANY OF THE DEFAULT SETTINGS DO NOT SUIT YOUR APPLICATION, GO TO THE ADJUSTING SECTION

THAT FOLLOWS EACH FUNCTION AND WRITE IN THE DESIRED SETTING IN THE SQUARE BOX

PROVIDED FOR THAT FUNCTION. THEN PERFORM THE ADJUSTMENT AS LISTED.

THESE INSTRUCTIONS ARE WRITTEN WHERE EACH FUNCTION IS ADJUSTED IN A

STAND ALONE

MANNER MEANING YOU ARE PROGRAMMING

THAT ONE FUNCTION ONLY

.

IF YOU WANT TO PROGRESSIVELY GO THROUGH EACH STEP

,

JUST SKIP THE INSTRUCTIONS WRITTEN IN

ITALIC

LETTERS FOR EACH STEP AND PROGRAM THE CONTROL PROGRESSIVELY THROUGH EACH FUNCTION

.

IT IS BEST IF YOU TAKE A FEW MINUTES TO GO THROUGH THE ENTIRE LIST OF FUNCTIONS AND

ENTER ANY NEW SETTINGS THAT ARE APPROPRIATE FOR YOUR INSTALLATION

.

WHEN FINISHED

,

GO TO THE CONTROL AND ADJUST ONLY THOSE FUNCTIONS THAT HAVE A NEW SETTING LISTED

.

Display

Description

Default

Setting

New

Setting

Room Occupied - The desired room air temperature during the occupied period.

Press the Menu button until ADJUST is visible on the top line of the display. Press the
Item button until ROOM appears above the temperature readout and OCC is flashing
below it. Use the up and down arrow buttons to change to the desired reading.
Range Available: 35˚ to 100˚F (2˚ to 38˚C)

70˚F

(21˚C)

Room Unoccupied - The desired room air temperature during the unoccupied period.

Press the Menu button until ADJUST is visible on the top line of the display. Press the
Item button until ROOM appears above the temperature readout and UNOCC is flashing
below it. Use the up and down arrow buttons to change to the desired reading.
Range Available: 35˚ to 100˚F (2˚ to 38˚C)

65˚F

(18.5˚C)