Ra + ra, Remote alarm led option 1 per unit – SilentKnight SK-Duct Addressable Photoelectric Duct Detector User Manual

Page 5

background image

SK-300-000

5

I56-3432-001R

*Aerosol smoke can be purchased from Home Safeguard Industries at home-
safeguard .com, model 25S Smoke Detector Tester, and Chekkit Smoke Detector
Tester model CHEK02 and CHEK06 available from SDi . When used properly,
the canned smoke agent will cause the smoke detector to go into alarm . Re-
fer to the manufacturer’s published instructions for proper use of the canned
smoke agent .

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary by
manufacturer . Misuse or overuse to these products may have long term adverse
effects on the smoke detector . Consult the canned smoke agent manufacturer’s
published instructions for any further warnings or caution statements .

[9]DETECTOR CLEANINg PROCEDURES
Notify the proper authorities that the smoke detector system is undergoing
maintenance, and that the system will temporarily be out of service . Disable
the zone or system undergoing maintenance to prevent unwanted alarms and
possible dispatch of the fire department .
[9.1]DETECTOR SENSOR
1 . Remove the sensor to be cleaned from the system .
2 . Remove the sensor cover by pressing firmly on each of the four removal

tabs that hold the cover in place .

3 . Vacuum the screen carefully without removing it . If further cleaning is re-

quired continue with Step 4, otherwise skip to Step 7 .

4 . Remove the chamber cover/screen assembly by pulling it straight out .
5 . Use a vacuum cleaner or compressed air to remove dust and debris from

the sensing chamber .

6 . Reinstall the chamber cover/screen assembly by sliding the edge over the

sensing chamber . Turn until it is firmly in place .

7 . Replace the cover using the LEDs to align the cover and then gently pushing

it until it locks into place .

8 . Reinstall the detector .
[9.2]REINSTALLATION
1 . Reinstall the detector in its housing .
2 . Restore system power .
3 . Perform Detector Check .
4 . Notify the proper authorities testing has been completed and the smoke

detector system is back in operation .

[10]SENSOR REPLACEMENT
1 . Remove the sensor head by rotating counterclockwise .
2 . Pull gently to remove it .
3 . To replace the sensor head, align the mounting features and rotate clock-

wise into place .

[11] OPTIONAL ACCESSORIES
Optional accessories include RA400Z/RA100Z, RTS451/RTS151 and RTS-
451KEY/RTS151KEY
fIgURE 8. wIRINg DIAgRAM fOR SK-DUCT TO RA400Z/RA100Z:

(+)

(-)

RA400Z/RA100Z

– RA

+ RA

REMOTE ALARM LED

OPTION 1 PER UNIT

H0570-03

Note: If using a RA400Z, the tab should be broken for use with the intelligent
duct smoke detector . If using RA100Z, ensure that jumper is removed .

[11.1]RTS451/RTS151, RTS451KEy/RTS151KEy REMOTE TEST STATION
wITh OPTIONAL TEST COIL
The RTS451/RTS151, RTS451KEY/RTS151KEY Remote Test Station facilitates
test of the alarm capability of the duct smoke detector . These accessories pro-
vide the stimulus to initiate an alarm condition at the detector . The SK-Duct
duct smoke detector must be reset by the system control panel .
NOTE: The use of a remote test station requires the installation of an acces-
sory coil, part number DCOIL, sold separately .

1) Install DCOIL in housing pocket insuring that arrow is pointing toward detector
2) Install DCOIL mounting screw
3) Connect each DCOIL lead to a Test Coil Terminal
See Figure 9 below for reference .
fIgURE 9. SK-DUCT wITh OPTIONAL TEST COIL

TEST COIL TERMINALS

TEST COIL

TEST COIL SCREW

H0561-01

fIgURE 10. wIRINg DIAgRAM fROM SK-DUCT TO RTS451/RTS151,
RTS451KEy/RTS151KEy:

EXTERNAL

(-) POWER (+)

SUPPLY

*

RTS451/151,

RTS451/151KEY

REMOTE TEST STATION

LED OPTION

1 PER UNIT

10mA CURRENT DRAW

TEST COIL OPTION

1 PER UNIT

95mA CURRENT DRAW

4

5

3

2

1

TEST COIL +

TEST COIL –

COMM +

OUT (CONV ONLY) +

COMM –

RA/RTS –

RA +

RTS +

NOTE: THE RTS451/151, RTS451/151KEY TEST COIL

CIRCUIT REQUIRES AN EXTERNAL 24 VDC POWER

SUPPLY WHICH MUST BE UL LISTED.

NOTE: THE USE OF A REMOTE TEST STATION REQUIRES THE

INSTALLATION OF AN ACCESSORY COIL, PART NUMBER DCOIL, SOLD

SEPARATELY.

H0571-07