Ra + ra, Remote alarm led option 1 per unit – SilentKnight SK-Duct Addressable Photoelectric Duct Detector User Manual
Page 5
SK-300-000
5
I56-3432-001R
*Aerosol smoke can be purchased from Home Safeguard Industries at home-
safeguard .com, model 25S Smoke Detector Tester, and Chekkit Smoke Detector
Tester model CHEK02 and CHEK06 available from SDi . When used properly,
the canned smoke agent will cause the smoke detector to go into alarm . Re-
fer to the manufacturer’s published instructions for proper use of the canned
smoke agent .
CAUTION
Canned aerosol simulated smoke (canned smoke agent) formulas will vary by
manufacturer . Misuse or overuse to these products may have long term adverse
effects on the smoke detector . Consult the canned smoke agent manufacturer’s
published instructions for any further warnings or caution statements .
[9]DETECTOR CLEANINg PROCEDURES
Notify the proper authorities that the smoke detector system is undergoing
maintenance, and that the system will temporarily be out of service . Disable
the zone or system undergoing maintenance to prevent unwanted alarms and
possible dispatch of the fire department .
[9.1]DETECTOR SENSOR
1 . Remove the sensor to be cleaned from the system .
2 . Remove the sensor cover by pressing firmly on each of the four removal
tabs that hold the cover in place .
3 . Vacuum the screen carefully without removing it . If further cleaning is re-
quired continue with Step 4, otherwise skip to Step 7 .
4 . Remove the chamber cover/screen assembly by pulling it straight out .
5 . Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing chamber .
6 . Reinstall the chamber cover/screen assembly by sliding the edge over the
sensing chamber . Turn until it is firmly in place .
7 . Replace the cover using the LEDs to align the cover and then gently pushing
it until it locks into place .
8 . Reinstall the detector .
[9.2]REINSTALLATION
1 . Reinstall the detector in its housing .
2 . Restore system power .
3 . Perform Detector Check .
4 . Notify the proper authorities testing has been completed and the smoke
detector system is back in operation .
[10]SENSOR REPLACEMENT
1 . Remove the sensor head by rotating counterclockwise .
2 . Pull gently to remove it .
3 . To replace the sensor head, align the mounting features and rotate clock-
wise into place .
[11] OPTIONAL ACCESSORIES
Optional accessories include RA400Z/RA100Z, RTS451/RTS151 and RTS-
451KEY/RTS151KEY
fIgURE 8. wIRINg DIAgRAM fOR SK-DUCT TO RA400Z/RA100Z:
(+)
(-)
RA400Z/RA100Z
– RA
+ RA
REMOTE ALARM LED
OPTION 1 PER UNIT
H0570-03
Note: If using a RA400Z, the tab should be broken for use with the intelligent
duct smoke detector . If using RA100Z, ensure that jumper is removed .
[11.1]RTS451/RTS151, RTS451KEy/RTS151KEy REMOTE TEST STATION
wITh OPTIONAL TEST COIL
The RTS451/RTS151, RTS451KEY/RTS151KEY Remote Test Station facilitates
test of the alarm capability of the duct smoke detector . These accessories pro-
vide the stimulus to initiate an alarm condition at the detector . The SK-Duct
duct smoke detector must be reset by the system control panel .
NOTE: The use of a remote test station requires the installation of an acces-
sory coil, part number DCOIL, sold separately .
1) Install DCOIL in housing pocket insuring that arrow is pointing toward detector
2) Install DCOIL mounting screw
3) Connect each DCOIL lead to a Test Coil Terminal
See Figure 9 below for reference .
fIgURE 9. SK-DUCT wITh OPTIONAL TEST COIL
TEST COIL TERMINALS
TEST COIL
TEST COIL SCREW
H0561-01
fIgURE 10. wIRINg DIAgRAM fROM SK-DUCT TO RTS451/RTS151,
RTS451KEy/RTS151KEy:
EXTERNAL
(-) POWER (+)
SUPPLY
*
RTS451/151,
RTS451/151KEY
REMOTE TEST STATION
LED OPTION
1 PER UNIT
10mA CURRENT DRAW
TEST COIL OPTION
1 PER UNIT
95mA CURRENT DRAW
4
5
3
2
1
TEST COIL +
TEST COIL –
COMM +
OUT (CONV ONLY) +
COMM –
RA/RTS –
RA +
RTS +
NOTE: THE RTS451/151, RTS451/151KEY TEST COIL
CIRCUIT REQUIRES AN EXTERNAL 24 VDC POWER
SUPPLY WHICH MUST BE UL LISTED.
NOTE: THE USE OF A REMOTE TEST STATION REQUIRES THE
INSTALLATION OF AN ACCESSORY COIL, PART NUMBER DCOIL, SOLD
SEPARATELY.
H0571-07