SilentKnight SD505-ADHR Addressable Duct Housing w/Relay User Manual
Sd505-adhr installation, Specifications mounting instructions

P/N 151126
SD505-ADHR Duct Detector Housing
With Relay Module & SD505-DTS
Installation Instructions
The following are instructions on how to install
the SD505-ADHR & SD505-DTS to a Silent
Knight Addressable control panel.
SD505-ADHR Installation
The SD505-ADHR is a duct detector housing
with a built-in relay module that is used to
control a fan motor to stop air flow in a fire
alarm situation.
Specifications
Mounting Instructions
Follow these steps to mount the SD505-ADHR:
1. Remove paper backing from mounting
template (packaged in installation kit) and
affix to duct at installation location.
2. Using the template as a guide, drill the four
mounting holes (3/32” diameter) for duct
detector mounting screws provided (4 # 12 x
1/2” sheet metal screws).
3. Use template as guide to drill or punch holes
for the sampling tubes in the air ducts (1-
3/8” diameter).
4. Clean all holes.
Sampling Tube Assembly
The sampling tubes can be ordered in standard
lengths and cut per requirements. See chart
below for available standard sizes. The intake
sampling tube is a piece of steel piping with a
series of holes drilled the entire length of the
tube. The tube should be cut to a size that allows
it to extend the entire width of the duct.
The holes must be facing into the air flow (see
Figure 1). The exhaust tube is a piece of steel
piping measuring 7 inches.
Specification Parameter
Rating
Alarm Relay Contact Rating:
10 A @ 120/240 VAC
Trouble Relay Contact Rat-
ing:
2.5 A @ 30VDC
Operating Volt-
age:
SLC
Loop:
32 VDC
Aux. Pwr.
Input:
120/240 VAC, 24 VDC/VAC
Aux. Input Power
Current:
24 VDC Standby:
35 mA
Alarm:
75 mA
24 VAC
Standby:
50 mA
Alarm:
90 mA
120 VAC Standby:
10 mA
Alarm:
20 mA
240 VAC Standby:
5 mA
Alarm:
10 mA
SLC Current for
Battery Calcula-
tions
Alarm:
.018 mA
Standby:
.018 mA
Max. SLC Loop Resistance:
50
Ω
Operating Temperature:
32° to 120° F (0° to 49° C)
Humidity:
10-85% RH
SD505-APS
SD505-AIS
Air Velocity:
500-4000 fpm 300-4000
fpm
Sensitivity:
0.85 to 1.15%
per foot
0.5 to 0.81%
per foot