Model 5495 Distributed Power Module Installation Manual

22

151161

4.8.3

Setting the Loss of AC Delay

Normal selection for reporting loss of AC is 3 hours.

The ON position is for test purposes only and the normal position for Switch 4 is OFF.
For testing the Low AC reporting, you can temporarily turn Switch 4 ON without
removing power.

Note: Remember to turn the switch OFF when testing is complete.

Figure 4-14 Setting DIP Switch 4

4.8.4

Setting the Auxiliary Output

Switch 5 on the DIP switch determines how the auxiliary power operates on the 5495.

The 5495 checks Switch 5 only when powering up the 5495. If you change this
switch, you must remove both the AC power and the battery to force the 5495 to
recognize the new switch setting.

Figure 4-15 Setting DIP Switch 5