beautypg.com

Reznor R6GF Option - Installation - Hard Start - Light Commercial User Manual

Warning, Installation instructions

background image

Universal Compressor Start Kit (No. 912933)

AboUt the StArt Kit

This compressor start kit includes the following items:

Description

Quantity

Compressor Start Assy ............................ 1
Mounting Brackets .................................... 2
Plastic Tie-Wrap ....................................... 1
Screws ...................................................... 4
Installation Instructions ............................. 1

Start Kits are designed to provide additional starting
torque for air conditioners or heat pumps equipped with
compressors using a permanent split capacitor (PSC)
single phase motor. This type of motor does not require a
start kit under normal operating conditions, but, because
low starting torque is inherent with PSC motors, special
conditions such as low voltage and exceptionally high
operating temperatures, short thermostat cycles, etc.,
can interfere with compressor starting.

• For Single Package Series Air Conditioners and Heat

Pumps use the vertical bracket as shown in Figure 2.

• For Single Package Gas/Electric Models, use the

horizontal bracket as shown in Figure 3.

• For Split System Air Conditioners and Heat Pumps no

bracket is necessary.

iNStALLAtioN SeQUeNCe

1. iMPortANt! Turn the power off to the unit.
2. Decide which application is required for the unit. The

starting relay is position sensitive and is marked UP on
the side of the relay. Make sure the relay is mounted

so that UP faces upward. See Figures 1-3 for proper

relay orientation.

3. Remove the control panel cover.

4. Attach the kit to the designated location in the control

panel with the provided screws. For split system units,

mount capacitor and relay at the designated locations
inside the control panel. Note: This relay may be
equipped with a universal bracket. With a pair of pliers,
break off any portion of the bracket that prevents proper
installation.

5. Attach the compressor start assembly to the proper

bracket using the capacitor strap and provided screws.
Note:

For split system units, omit this step.

6. Connect the bLACK

wire (Figure 1) from

terMiNAL

5 on the start relay to t2 on the contactor.

7. Connect the reD wire from terMiNAL 2 on the start

relay to the compressor capacitor terminal marked h

(or HERM).

8. Connect the YeLLow wire from one terminal of the

start capacitor to the compressor capacitor terminal
marked C (or COMMON). Note: Terminals 4 & 6 (if
available on your relay) are not used for this application.

eLeCtriCAL ShoCK, Fire or

eXPLoSioN hAZArD

Failure to follow safety warnings exactly could
result in serious injury or property damage.

improper servicing could result in dangerous
operation, serious injury, death or property
damage.

• Before servicing, disconnect all electrical

power to furnace.

• When servicing controls, label all wires prior

to disconnecting. reconnect wires correctly.

• Verify proper operation after servicing.

wArNiNG:

iNStALLAtioN iNStrUCtioNS

iMPortANt SAFetY iNForMAtioN

these instructions are primarily intended to assist
qualified individuals experienced in the proper
servicing of heating and air conditioning appliances.
Some local codes require licensed installation / service
personnel for this type equipment. Use of this kit must

be in accordance with these instructions and with all
applicable national and local codes and standards.
INSTALLER: Please read all instructions thoroughly

before servicing this equipment. Pay attention to all safety
warnings and any other special notes highlighted in the
manual. Safety markings are used frequently throughout
this manual to designate a degree or level of seriousness
and should not be ignored.

wArNiNG - Indicates a

potentially hazardous situation that if not avoided, could
result in personal injury or death.

CAUtioN - Indicates

a potentially hazardous situation that if not avoided, may
result in minor or moderate injury or property damage.

wArNiNG:

the safety information listed in this manual must

be followed during the installation, service, and

operation of this unit. Unqualified individuals
should not attempt to interpret these instructions
or install this equipment. Failure to follow safety

recommendations could result in possible

damage to the equipment, serious personal
injury or death.