1. Remove

green wire from blower relay and

discard. Connect new green wire to the fan
delay relay terminal #4 (terminal #5 on some
models) and route to “G” at thermostat.

2. Attach

new blue wire between terminal #1

on fan delay relay and terminal where the
green wire has been removed from blower
relay in the previous step.

3. Locate black wire connecting blower relay

coil common terminal and transformer.
Remove wire at transformer.

4. Attach new gray wire to the time delay relay

terminal #3 and the transformer terminal

Figure 1. Wiring Diagram for Single Package Air Conditioners and

Heat Pump Applications.

where black wire was removed in step 3
(piggy back terminal). Re-connect the black
wire removed in step 3 to the piggy back
terminal at transformer.

5. Locate

the

red wire connecting to the fuse at

the transformer. Cut the wire at a convenient
location and strip both ends at the cut. Strip
the new red wire at the piggy back terminal.
Twist all three wire ends together and secure
with a wire nut. Connect the straight terminal
of the red wire to terminal #2 on the fan delay
relay.

6. Complete installation as outlined in “General”

instructions on page 1

* Wires marked with an asterisk (*) are supplied as part of the TDR kit.
† labeled as teminal #5 on some models

1

3

T2

L2

TRANSFORMER

BLOWER


RELAY

UNIT
CONTACTOR

TIME DELAY RELAY

TO BLOWER MOTOR

24V

2

4†

RED

BLACK

BLACK

RED

*

GRAY

*

GREEN

*

BLUE

*

TO "G" ON
T'STAT

TO "R"
TERMINAL

SPLICE/
SECURE

RED

FUSE