Installation instructions, Installation instructions concentric diffuser – Reznor R6GP Option - Installation - Concentric Diffuser - Light Commercial User Manual
Page 6

INSTALLATION INSTRUCTIONS
CONCENTRIC DIFFUSER
INSTALLATION
INSTRUCTIONS
DI MEN SIONAL DATA
MODEL#
A
B
C
D
E
F
G
H
I
J
K
L
M
DUCT SIZE
547880
47
5
8
35
5
8
20
5
8
33 ½
45 ½
4 ½
18
2 ½
28
2 ¾
45 ½
33 ½
9
1
8
18x28
555639
47
5
8
41
5
8
24
5
8
39 ½
45 ½
4 ½
18
2 ½
32
3 ¾
45 ½
39 ½
9
1
8
18x32
555640
47
5
8
47
5
8
24
5
8
45 ½
45 ½
4 ½
18
2 ½
36
4 ¾
45 ½
45 ½
10
1
8
18x36
DI MEN SIONAL DATA
MODEL#
A
B
C
D
E
F
G
H
I
J
K
DUCT SIZE
547838
47
5
8
23
5
8
11
3
8
21 ½
45 ½
22 ½
11 ½
10 ¾
45 ½
21 ½
7
1
8
16 RD
547839
47
5
8
23
5
8
11
3
8
21 ½
45 ½
22 ½
11 ½
10 ¾
45 ½
21 ½
7
1
8
18 RD
547871
47
5
8
29
5
8
14
3
8
27 ½
45 ½
22 ½
11 ½
13 ¾
45 ½
27 ½
8
1
8
20 RD
Form# RSI-CI-N
SUPERSEDES 10-12-04
JULY 22, 2011
EN GI NEER ING DATA
MODEL#
CFM
STATIC
PRES SURE
THROW
FEET
NECK/JET
VEL.
NOISE
LEVEL
547880
3600
.17
25-33
851
30
3800
.18
27-35
898
30
4000
.21
29-37
946
30
4200
.24
32-40
993
30
4400
.27
34-42
1040
30
555639
4600
.31
26-31
841
30
4800
.32
27-32
878
30
5000
.34
28-33
915
30
5200
.36
28-34
951
30
5400
.39
29-35
988
30
555640
5600
.36
39-49
920
30
5800
.39
42-51
954
30
6000
.42
44-54
1022
30
6200
.46
45-55
1056
30
6400
.50
46-55
1090
30
6600
.54
47-56
1124
30
NOTES:
1. All data is based on the Air Dif fu sion Coun cil guide lines.
2. Throw data is based on Ter mi nal Ve loci ties of 75 FPM us ing
iso ther mal air.
3. Ac tual noise lev els are less than those shown.
4. Throw is based on diffuser blades being directed in a straight
pattern.
EN GI NEER ING DATA
MODEL#
CFM
STATIC
PRES SURE
THROW
FEET
NECK/JET
VEL.
NOISE
LEVEL
547838
600
.09
8-15
210
20
800
.11
9-16
281
20
1000
.14
10-17
351
20
1200
.17
11-18
421
20
547839
1200
.17
11-18
421
20
1400
.20
12-19
491
20
1600
.24
12-20
561
20
1800
.30
13-21
632
20
2000
.36
14-23
702
20
2200
.40
16-25
772
20
547871
2600
.17
24-29
669
20
2800
.20
25-30
720
25
3000
.25
27-33
772
25
3200
.31
28-35
823
25
3400
.37
30-37
874
30
NOTES:
1. All data is based on the Air Dif fu sion Coun cil guide lines.
2. Throw data is based on Ter mi nal Ve loci ties of 75 FPM us ing
iso ther mal air.
3. Ac tual noise lev els are less than those shown.
4. Throw is based on diffuser blades being directed in a straight
pattern.
- Q6SP Option - Installation - Concentric Diffuser - Light Commercial P6SP Option - Installation - Concentric Diffuser - Light Commercial R8GD Option - Installation - Concentric Diffuser - Light Commercial R6GD Option - Installation - Concentric Diffuser - Light Commercial Q6SD Option - Installation - Concentric Diffuser - Light Commercial P6SD Option - Installation - Concentric Diffuser - Light Commercial R6GI Option - Installation - Concentric Diffuser - Light Commercial R6GN Option - Installation - Concentric Diffuser - Light Commercial