Installation instructions, Installation instructions concentric diffuser – Reznor R6GP Option - Installation - Concentric Diffuser - Light Commercial User Manual
Page 5
![background image](/manuals/709576/5/background.png)
INSTALLATION INSTRUCTIONS
CONCENTRIC DIFFUSER
INSTALLATION
INSTRUCTIONS
DI MEN SIONAL DATA
MODEL#
A
B
C
D
E
F
G
H
I
J
DUCT SIZE
547879
47
5
8
35
5
8
23 ¼
33
45
4 ½
18
2 ¼
28
2 ½
18x28
555637
47
5
8
41
5
8
29 ¼
39
45
4 ½
18
2 ¼
32
3 ¼
18x32
555638
47
5
8
47
5
8
29 ¼
45
45
4 ½
18
2 ¼
36
4 ½
18x36
DI MEN SIONAL DATA
MODEL#
A
B
C
D
E
F
G
H
DUCT SIZE
547836
47
5
8
23
5
8
13 ½
21
45
22 ½
11 ¼
10 ½
16 RD
547837
47
5
8
23
5
8
13 ½
21
45
22 ½
11 ¼
10 ½
18 RD
547870
47
5
8
29
5
8
16
5
8
27
45
22 ½
11 ¼
13 ½
20 RD
EN GI NEER ING DATA
MODEL#
CFM
STATIC
PRES SURE
THROW
FEET
NECK
VEL.
JET VEL.
NOISE
LEVEL
547879
3600
.17
22- 29
844
1646
35
3800
.18
22- 30
891
1737
40
4000
.21
24- 33
938
1829
40
4200
.24
26- 35
985
1920
40
4400
.27
28- 37
1032
2011
40
555637
4600
.31
25- 34
922
1795
40
4800
.32
26- 35
962
1873
40
5000
.34
27- 36
1002
1951
40
5200
.36
30- 39
1043
2029
45
5400
.39
32- 41
1083
2107
45
555638
5600
.36
28- 37
1000
2082
45
5800
.39
29- 38
1036
2156
45
6000
.42
40- 50
1071
2230
45
6200
.46
42- 51
1107
2308
50
6400
.50
43- 52
1143
2379
50
6600
.54
45- 56
1179
2454
50
NOTES:
1. All data is based on the Air Dif fu sion Coun cil guide lines.
2. Throw data is based on Ter mi nal Ve loci ties of 75 FPM us ing
iso ther mal air.
3. Ac tual noise lev els are less than those shown.
EN GI NEER ING DATA
MODEL#
CFM
STATIC
PRES SURE
THROW
FEET
NECK
VEL.
JET VEL.
NOISE
LEVEL
547836
600
.09
10- 14
234
417
18
800
.11
12- 18
313
556
20
1000
.14
15- 20
391
694
20
1200
.17
16- 22
469
833
25
547837
1200
.17
16- 22
469
833
25
1400
.20
17- 24
547
972
30
1600
.24
18- 25
625
1111
30
1800
.30
20- 28
703
1250
35
2000
.36
21- 29
781
1389
40
2200
.40
22- 30
859
1528
40
547870
2600
.17
19- 24
663
1294
30
2800
.20
20- 28
714
1393
35
3000
.25
21- 29
765
1492
35
3200
.31
22- 29
816
1592
40
3400
.37
22- 30
867
1692
40
NOTES:
1. All data is based on the Air Dif fu sion Coun cil guide lines.
2. Throw data is based on Ter mi nal Ve loci ties of 75 FPM us ing
iso ther mal air.
3. Ac tual noise lev els are less than those shown.
- Q6SP Option - Installation - Concentric Diffuser - Light Commercial P6SP Option - Installation - Concentric Diffuser - Light Commercial R8GD Option - Installation - Concentric Diffuser - Light Commercial R6GD Option - Installation - Concentric Diffuser - Light Commercial Q6SD Option - Installation - Concentric Diffuser - Light Commercial P6SD Option - Installation - Concentric Diffuser - Light Commercial R6GI Option - Installation - Concentric Diffuser - Light Commercial R6GN Option - Installation - Concentric Diffuser - Light Commercial