High pressure cut out 
This is pressure limit which is set 10-20% higher than desired 
operating pressure. When high pressure cut out pressure is 
reached controller will cause main control valve to close. 
 
 
 
 
 
 
 
1.
Press NEXT key three times and following screen will 
appear: 
Screen 4 
HIGH PRESSURE 
2.
Press SELECT key and screen will read:
Screen 4 
HIGH PRESSURE 
CUT OFF PSI [XXX] 
 
3.
Press NEXT key to scroll through pressure settings until 
desired pressure setting appears on screen.. Settings from 
0-50 psi are in 1 psi increments and from 50 through 150 
psi in 5 psi increments. NOTE: MAXIMUM SETTING 
IS LIMITED BY RANGE OF PRESSURE SENSOR. 
high pressure setting should be set lower than 
relieving pressure ASME relief valve supplied with 
generator. Pressure rating of relief valve is labeled on 
relief valve body. 
4.
Press SELECT key to place setting in memory and return 
to home screen. 
 
Low pressure alarm 
If desired a low pressure alarm can be set. This will alarm if 
generated steam pressure falls below low pressure setting. 
 
To set low pressure alarm: 
 
1.
Press NEXT key four times and following screen will 
appear: 
Screen 5 
LOW PRESSURE 
 
2.
Press SELECT key and screen will read:
Screen 5 
LOW PRESSURE 
ALARM PSI [XXX] 
 
3.
Press NEXT key to scroll through pressure settings 
until desired low pressure setting appears on screen.. 
Settings from 0-50 psi are in 1 psi increments. 
Maximum low pressure setting is equal to high pressure 
setting set on screen 4. 
4.
Press SELECT key to place setting in memory and 
return to home screen. 
NOTE: To disable low pressure alarm set pressure to zero (0).
 
High and low pressure reset differential 
This is pressure differential from set point at which high or 
low pressure will reset. Normally it is set at 2 psi but can be 
set from 1 to 10 psi. NOTE: There is only one differential 
setting and it will be same for both high and low pressure. 
 
To set pressure differential: 
1.
Press NEXT key five times and following screen will 
appear: 
Screen 6 
DIFFERENTIAL 
 
2.
Press SELECT key and screen will read:
Screen 6 
DIFFERENTIAL 
RESET PSI [XXX] 
 
3.
Press NEXT key to scroll through psi settings until 
desired psi differential is displayed. Range is 1-10 psi. 
4.
Press SELECT key to place setting in memory and 
return to home screen. 
 
Setting Pressure Sensor Range 
pressure sensor supplied with Unfired Steam Generator will 
have a specific range, normally 0-30 psi or 0-60 psi or 0-150 
psi. It is extremely important that range of pressure 
sensor and range listed in solid state controller be same 
range. Generator is factory shipped with matched ranges. 
Range of sensor will be printed on body of sensor. Range of 
controller can be determined and if necessary changed as 
follows: 
 
1.
Press NEXT key six times and following screen will 
appear: 
Screen 7 
 PRESSURE SENSOR 
2.
Press SELECT key and screen will read:
Screen 7 
 PRESSURE SENSOR 
RANGE PSI [XXX] 
3.
Verify that psi range shown is equal to range of supplied 
sensor. Range shown on screen is upper end of range. 0-
30 will appear as 30 on screen, 0-60 will appear as 60 on 
screen , etc. IF AND ONLY IF range of sensor is 
different than screen setting should screen setting be 
changed. To change screen setting press NEXT key to 
scroll through various pressure settings. Available ranges 
are 30-150 psi in 10 psi increments. When desired 
pressure range appears on screen verify that this matches 
pressure of sensor. 
4.
If both pressures match press SELECT key to place 
setting in memory and return to home screen. 
CAUTION
Operating pressure is set by control valve controller, 
see USG I O & M manual for setting operating 
pressure. 