Building automation control (bac) interface, Caution – Leslie Controls Unfired Steam Generator LVSG SERIES User Manual
Page 10

- 10 -
 
 
 
 
 
Building Automation Control (BAC) 
Interface 
LESLIE 2001 SSCM has built in contacts to interface with 
building automation control (BAC). 
 
Remote On-Off: 
Terminal block P-2 is a three pole block with two outside 
poles connected in series with 24 VAC incoming power from 
supply transformer. Unfired Steam Generator is shipped with 
a jumper installed between terminals 1- 3 of terminal block P-
2. To wire for remote on-off remove this jumper and install a 
switch or relay contacts connecting terminals 1 and 3. Do not 
connect anything to terminal 2 of P-2. 
 
 
 
 
 
 
 
Built in contacts to notify BAC of functions and alarms: 
This control allows for simple and reliable interface with BAC 
via dry contact to enable BAC to monitor following functions 
from a remote location: 
Power ON 
Low water 
High water 
Water feed 
High pressure 
Low pressure 
Blow down operating 
Optional input / output 
Alarm 
 
Refer to “Terminal Board Layout” page of this manual for key 
to and location of terminal connections to BAC. Note that all 
of function relays give either a COM-NO or COM-NC dry 
contact output. Rating of dry contacts are 1 amp at 24 VAC or 
.5 amp at 120 VAC.
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Contact closure as follows: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Operating pressure (via a 0-10 VDC signal); 
Terminal block I-2 will output a 0-10 VDC signal. This 
signal will be scaled to pressure range of supplied pressure 
sensor. To scale BAC : Determine pressure range printed on 
body of supplied sensor and scale 0-10 VDC output signal to 
this range. This range should 
 also be listed in submittal supplied for generator.
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Power
ON
 
 
COM - NO contact made when 
power is on 
Low
water
 
 
COM - NO contact made when in 
low water condition 
High
water
 
 
COM - NO contact made when 
high water occurs 
Water
feed
 
 
COM - NO contact made when 
water is feeding 
High pressure
 
 
COM - NO contact made when 
high pressure occurs 
Low pressure
 
 
COM - NO contact made when 
low pressure occurs 
Blow
down
operating
 
COM - NO contact made when 
blow down occurs 
Optional input
 
COM - NO contact made when 
optional contact close 
Alarm 
 
 
COM - NO contact made when any 
alarm occurs 
CAUTION
TERMINALS 1 -3 ARE 24 VAC AND WILL HAVE 
A LOAD OF 1 AMP. BE SURE SWITCH OR 
RELAY CONNECTED TO THESE TERMINALS IS 
RATED FOR A MINIMUM OF 24 VAC 1 AMP
.
CAUTION
Do not connect any voltage above 120 volts across 
BAC contacts on terminal block.. 
CAUTION
bottom terminal of 1-2 is connected to an isolated 
chassis ground. This may interfere with BAC 
system. BAC engineering should determine if BAC 
needs isolation for this signal.  
CAUTION
No current should be applied to terminals I-2.