Contractor wiring – Leslie Controls Unfired Steam Generator LVSG SERIES User Manual
Page 4

- 4 -
 Solid State Control Module is supplied with a LED backlit 
LCD display. LED pilot lights are supplied to indicate On-
Off, high pressure, low pressure, low water, high water, water 
feed, and blow down. Solid state control module allows 
owner to set pressure limits on display screen. Solid state 
control module has a flashing red alarm light and alarm horn 
with built in alarm silence relay. Solid state control module is 
supplied with dry contact closure outputs to indicate to 
building automation control ( BAC) Power on, Low water, 
High pressure, Water feed, High water, Low pressure and 
Blow down occurring. Control module allows BAC to turn 
Unfired Steam Generator on or off through a remote relay 
suitable for 24 VAc, 1 amp. Control module allows BAC to 
remotely monitor operating pressure. Control module is 
supplied with an on-off switch and is mounted in a NEMA 4 
enclosure. 
 
Built in remote start stop: This feature allows Unfired Steam 
Generator to be started or stopped from a remote location. 
Typically this would be accomplished from Building 
Automation Control (BAC) . Requires a dry contact suitable 
for 24 VAc and 1 amp. Terminals P2 on panel are where BAC 
on-off is wired. 
 
Built in On-Off Switch: Allows for local on-off and is 
convenient for service in unlikely event service is required. 
This switch is mounted in side of panel. 
 
Built in Alarm Horn: alarm horn will sound and fault LED 
will light (blinking red) on low water or high pressure If 
either high water or low pressure options are selected alarm 
horn will also sound and alarm light will light (blinking red) 
in event of high water or low pressure. 2001 Solid State 
Control Module also features an alarm silence relay which 
will silence alarm but not fault light when generator is being 
serviced. When fault is cleared both alarm and fault light will 
automatically reset. 
 
Built in timer for timed blow down: If timed blowdown option 
is selected time and duration of blow down can be easily 
selected in Leslie 2001 Solid State Control Module. 
 
Built in relay for water feed: Leslie 2001 Solid State Control 
Module operates in conjunction with level control to signal 
feed water solenoid or feed water pump to maintain correct 
water level in unfired steam generator. 
 
Built in operating pressure readout: Leslie 2001 Solid State 
Control Module features an easy to read LED digital readout 
of operating pressure. 
 
Built in high pressure cut off and alarm: In event of high 
pressure Leslie 2001 Solid State Control Module will close 
source steam or HTHW supply valve and sound an alarm. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Built in low water cut off and alarm: In event of low water 
Leslie 2001 Solid State Control Module will close source 
steam or HTHW supply valve and sound an alarm. 
 
Built in low pressure alarm: If activated, Leslie 2001 Solid 
State Control Module will sound an alarm if a low pressure 
condition occurs. 
 
Built in optional input / output. 
Built in LED display of functions and alarms: Leslie 2001 
Solid State Control Module is designed for user to tell at a 
glance how system is operating. Built in LED displays make 
troubleshooting simple. 
 
Function 
LED Indicator 1
LED Indicator 2
Power ON
Green = Power 
On 
Blank = No power
Low water
Green = Water 
level not low 
Red = Low water
High 
pressure 
Green = Normal 
pressure 
Red
=
High
pressure
Water feed
Green = Water 
feeding 
Blank = Water not 
called for 
High water
Green = Water 
level normal 
Red = High water
Low 
pressure 
Green = Pressure 
not low 
Red
=
Low
pressure
Blow down 
operating 
Green=Blowdown 
occurring 
Blank
=
No
Blowdown
Optional 
input/output 
 
 
Built in contacts to notify BAC (Building Automation 
Control) of functions and alarms: This control allows for 
simple and reliable interface from a remote location. BAC can 
also start and stop unfired steam generator. 
Contractor Wiring
 
All Power Connections should be performed by a trained, 
certified electrician. Be sure factory supplied on-off 
switch is in OFF position before connecting to building 
power. 
Power ON 
Low water 
High water 
Water feed 
High pressure 
Low pressure 
Blow down operating 
Optional input / output 
Alarm 
Operating pressure (via a 0-10 Vdc 
signal) 
