Screen 5
Screen 6
LOW PRESSURE
DIFFERENTIAL
Screen 7
Screen 8
PRESSURE SENSOR
LEVEL CONTROL
Screen 9
Screen 10
INITIAL SETTINGS
DIAGNOSTICS
Screen 11
Screen 12
ABOUT
QUIT
 
 
 
 
 
 
 
There are two tactile keys on front of panel. Left key, labeled 
NEXT, is pushed to select desired function. Right key, 
labeled SELECT, is pushed to access desired screen. Both 
function and setting are read on LED backlit LCD display. 
sequence to access and change any screen is as follows: 
1. Press “NEXT” (left key) key until desired function
appears on screen.
2. Press “SELECT” (right key) and a setting will appear on
second line of screen.
3. Press “NEXT” key to change setting . Continue pressing
“NEXT” key, which will scroll though available settings 
until desired setting is on screen. 
4. Press “SELECT” key which will store last screen setting
into memory and return to controller screen to “HOME”
Instructions for Setting Each
Screen
Home Screen 
This is screen which should be displayed during normal 
operation: 
Screen 1 (Home) 
MODE 
[NORMAL] PRESSURE PSI [XXX] 
 
MODE can be either NORMAL or ALARM. Mode will read 
normal in normal operation and alarm if any alarm condition 
occurs. If an alarm condition is cleared mode will switch back 
to normal reading. 
 
Pressure psi: This is pressure of generated steam. 
 
Timed Blow down 
 If timed blow down is a option which was purchased duration 
and interval of blow down can be selected. Duration is length 
of time blow down occurs (in seconds) and interval is number 
of hours between blow downs. 
 
To set duration of blow down: 
1.
Press NEXT key once and following screen will appear.
Screen 2 
BLOW DOWN DURATION 
 
2.
Press SELECT key and screen will read.
Screen 3 
BLOW DOWN DURATION 
SECONDS [XXX] 
 
3.
Press NEXT key to scroll through various seconds 
settings until desired number of seconds of blow down 
appears on screen. seconds will read 0-250 seconds in 10 
second increments. 
4.
Press SELECT key to place setting in memory and to 
return to home screen. 
NOTE: To disable timed blow down set duration to zero (0) 
 
To set interval: 
1.
Press NEXT key twice and following screen will 
appear: 
Screen 3 
B_DOWN INTERVAL 
 
2.
Press SELECT key and screen will read:
Screen 3 
B- DOWN INTERVAL 
HOURS [XXX] 
 
3.
Press NEXT key to scroll through various hour settings 
until desired number of hours between blow downs 
appears on screen. Hours will read 0-30 hours in one 
hour increments and 40 through 160 hours in 10 hour 
increments. 
4.
Press SELECT key to place setting in memory and 
return to home screen. 
 
NOTE: To disable timed blow down set interval to zero (0) 
 
CAUTION!
Conduit and piping system must be adequately 
designed and supported to prevent extraordinary loads 
to pressure/ electrical equipment. 