Troubleshooting – Leslie Controls NYC Heat Exchanger User Manual
Page 17

Page 17 of 25
 
 
Valve Listing and Functions (refer to assembly drawing for particular size heater) 
Item No. 
ON
OFF
15
Flow diverter, primary flow to Pump 1, no flow to 
pump 2 
No flow to pump 1, flow to pump 2
16
Emergency pressure relief, flow to drain
No flow to drain
37
Hand Op Ball, re-circulation water to Cold inlet 
water 
No re-circulation water to Cold inlet 
water 
39
Gain Adjuster Valves
Adjust cold water flow to insure constant 
temperature over the range of flow. 
41
Hand Op. Ball, Supply cold water to blend valve
Shut off cold water to blend valve
42
Blend Valve, 150 F, Blending Water
No blending of water
43
Blend Valve, 130 F, Blending Water
No blending of water
46
Check Valve, no back flow of hot water from heat 
exchanger 
N/A
47
Solenoid Valve, Hot water to second blend valve
No hot water to second blend valve
59
Gate valve, Supply steam
Shut off steam supply
68
Hand Op Ball, Bypass condensate cooler
Flow through condensate cooler
76
Gate valve, flow of condensate to drain
No flow of condensate to drain
78
Needle valve, Steam to gauge and pressure sensor
Shut of steam for maintenance of gauge
101
Condensate Diverter, Condensate through Cooler
Condensate
to
drain
and
bypass
Condensate Cooler in fail mode.
 
 
 
 
TROUBLESHOOTING
Condition
Possible Cause
Fix
No Steam/Low Steam
Adjust steam regulator.
Blocked tubes in heat exchanger
Flush Heat exchanger.
Drain valves from steam traps are shut
Open drain valves.
Condensate drain line is blocked or valves are turned off
Clear line and turn on valves.
Solenoid is tripped
Turn on Manual switches “H-1” and 
H-2” 
Blend valve element defective
Test blend valve element and replace if 
necessary. 
 
 
 
 
No Hot water 
Over temperature condition was reached and Thermo Switches 
are still engaged. 
Find out why over temperature 
happened and let Thermo Switches 
reset. 
Shut of the Gain adjusters
Cold water main from street is shut off. 
Reset Gain Valves (39) 
Steam pressure above 15 psi
Steam adjust steam pressure or fix 
steam regulator. 
Steam Traps broken and steam is being sent to the condensate 
cooler 
Fix Steam traps.
 
 
 
System 
Tripped 
Blend valve element defective.
Test blend valve element and replace if 
necessary. 